Appendix 3 Technical Specifications
87%
Efficiency
120~253Vac
Bypass voltage
105~125% rated load, 5min; 125~150% rated load, 10s
Inverter overload
capacity
≤
60mS
Transient
recovery time
5% at 100% load step change resistive load
Dynamic
response
≤
3% linear load
≤
5% nonlinear load
Voltage harmonic
distortion
3:1
Crest factor
0.7
Power factor
≤
1Hz/s
Frequency
synchronization
speed
Synchronizes with the mains frequency when the mains is
working; 50Hz 0.2% when in Battery mode.
Frequency
220Vac±2%
Voltage
3kVA/2.1kW
2kVA/1.4kW
1kVA/700W
Power rating
Output
≥
0.99
Power factor
50Hz±5Hz
Frequency
160-276Vac: 100% rated load; 120-160Vac: linear derating in
loading; 120Vac: 50% rated load
Voltage range
220Vac
Rated voltage
Input
UH11-0030L
UH11-0020L
UH11-0020LB
UH11-0010L
UH11-0030
UH11-0020
UH11-0020B
UH11-0010
Model
Appendix 3 Technical Specifications 47
E1-20010915-C-1.0