Figure 1: Bella I/IPS wiring (not including the AS version)

 

 

Step Three: Powering-up 

1. After the wiring to the panel is completed, re-check the polarity 
2. Close the siren cover to prevent alarm caused by the Bella tamper switch 
3. Power-up the control panel. 

 
Step Four: Testing 

Close  the  Bella  box.  Generate  alarm  condition;  check  if  siren  and  strobe  are 
functioning correctly. Bella circuitry is protected against high voltage supplied (over 
14V) to +TRG, if such supplied the siren operation is blocked. 
Open  the  box  for  Tamper  alarm  test,  verify alarm  generated.  Close  the  cover and 
tight  the  screw  mounted  in  the  front  face.  Note:  Consider  strobe  lens  cleaning 
service once a year

 
 

B e l l a   I   S p e c i f i c a t i o n s  

Operating Temp: -25 to +60 C° 

Strobe source: High Power LEDs (3) 

Humidity: 80% 

Strobe output: 40,000 candles 

DC Input: 11 – 14.2V 

Cabinet Type: ABS @ IP55 

Standby Current: 20 mA 

Piezo Siren: Reflexive Piezo Ceramic 

Current (Sir & Strobe): 0.25 @IPS/ 0.38A 

Tamper: Wall Removal & Case Open 

Sound level: 110 dB @ 1 m 

Size: H=22, W=15, D=9 (cm) 

Strobe flash rate: One per 2 seconds 

Weight: 1 kg 

 
 

® All rights reserved to Av-Gad Systems Ltd, BELLA I LEDS & 1 INS AND MANUAL ENG.DOC, June 2018 

 
 