7
Enabling input function
To turn on the function of input, you can send the following commands by SMS message to
the unit.
#CTR=
X
X stands for ON (
1
) or OFF (
0
) value
To turn on the input, the syntax of the command is the following:
# PWD123456#CTR=1
Setting the Counter Alert Value For Input
An alert message will be sent when the increment of alarm counter reaches the alert value
(
Default: 500
). It is possible to set the alert value up to maximum value of 65535 times. To
set the counter alert value of input, you can send the following commands by SMS
message to the unit.
Text Command:
#COA=
XXXXX
XXXXX stands for
5
digits value: The number of times
For example, assume you want it to send a counter alert message each time the input has
been triggered for 5 times, you would send the following SMS message to the unit.
#PWD123456#COA=00005
Input behave setting
This input can be programmed to behave differently: it can count the input active high
pulses, generate an alarm message or activate relay. To program the input, you can send
the following commands by SMS message to the unit.
Text Command:
#CTC=
F
F stands for input function
1
-
5
Function Descriptions
Function
1
:
Functions as counter.
Sends a counter alert message once the alarm counter reaches the alert value.
Function
2
:
Functions as counter.
Activates the output relay 2 to stay on.
Sends a counter alert message once the alarm counter reaches the alert value.