AUX-DC inverter ARV outdoor unit individual series technical manual
128
4.2 Refrigerant system protection
Code
Error code definition
Recovery
or not
Possible reason
E3
High discharge
temperature protection.
No
1. System less refrigerant
2. ODU heat exchanger is dirty
3. There is air or N
2
in the piping system
4. Compressor suction pipe is blocked
5. Gas/liquid side stop valve is closed
6. Outdoor unit PCB failure
F3
High pressure protection.
Yes
1. Exhaust pipe or condenser pipe is blocked
2. Condenser is dirty
3. Outdoor unitfan is stopped orlow speed
4. Refrigerant overcharge
F6
Low pressureprotection.
No
1. Indoor unit fan is failed
2. Evaporator is dirty.
3. Lack refrigerant
4. Suction pipe is blocked.
F8
High Compression ratio
protection
No
1. The discharge pipe of outdoor unit is blocked.
2. The suction pressure is too low, refer to F6.
F9
Low compression
ratioprotection
No
1. The 4-way valve is failed because of block or high temperature.
2. Refrigerant return to the compressor is mixed with liquid and gas
because of poor evaporation.
FA
No difference between high
and low pressure
Yes
The 4-way valve is failed because of block or high temperature.
H5
Lack of refrigerant
No
1. There is refrigerant leakage.
2. Additional refrigerant charging volume is not enough.
JJ
Indoor unit total capacity
exceeding
Yes
Capacity of indoor units is less than 50% or more than 130% of
outdoor unit capacity.
4.3 Electric control system failure and protection
Code
Error code definition
Recovery
or not
Possible reason
HJ
Main power failure
No
1. Supply power phase-reversal
2. Supply power phase lack
3. Outdoor unit PCB failure
J2
Communication error
between outdoor and
indoor unit.
Yes
1. Short or Open circuit?
2. IDU address code is repeated?
3. Indoor power supply is abnormal?
4. Hand in hand connection?
5. Too closed to the strong power?
6. The wire is too long?
7. Outdoor / indoor PCB failure?
Summary of Contents for ANB66FVAMT
Page 1: ...AUX DC inverter ARV individual series 1 Technical Manual DC Inverter ARV Individual Series ...
Page 3: ...AUX DC inverter ARV individual series 3 ...
Page 19: ...AUX DC inverter ARV outdoor unit individual series technical manual 16 ...
Page 21: ...AUX DC inverter ARV outdoor unit individual series technical manual 18 ...
Page 96: ...AUX DC inverter ARV outdoor unit individual series technical manual 93 ...
Page 113: ...AUX DC inverter ARV outdoor unit individual series technical manual 110 ...
Page 127: ...AUX DC inverter ARV outdoor unit individual series technical manual 124 ...