Equivalent pipe length conversion
Equivalent pipe length means converting pipe elbow to straight pipe length after considerate
the pressure loss.
Elbow and Oil loop conversion tablet
Type
Pipe Dia.(mm)
Bend
Oil Loop
6.35
0.10
0.7
9.52
0.18
1.3
12.70
0.20
1.5
15.88
0.25
2.0
19.05
0.35
2.4
22.02
0.40
3.0
Equivalent pipe length L
=
Actual Pipe length L+ Bend Qty× Equivalent pipe bend Oil
Loop Qty× Equivalent Oil Loop length
Sample:
AMCA-H09/4R3AActual Pipe length is 25 meters, Gas pipe diameter is 9.52mm. If there’s 5
bends and 2 oil loops during the installation, then the equivalent pipe length should be:
L=25+0.18×5+1.3×2=28.5(m)
9. Emptying or vacuum
Before charging the refrigerant to the system, to ensure that there is no impurities, water or
non-condensable gas. So, emptying and vacuum operation should be carried out.
◇
Vacuum: when process this operation please be sure that the connection pipe is tightened
up.
1. Screw off the cover of maintenance valve connection, connect the pressure gauge to the
connection of maintenance valve
2. Connect the vacuum pump to the pressure gauge, turn on the vacuum pump and pressure
gauge to process the vacuum operation toward the indoor unit and piping, while to ensure that the
absolute pressure is no less than 50Pa after this operation.
Summary of Contents for AMWM-H07/4R3
Page 54: ...AUX DC Inverter Free Match 50HZ R32 3 Ceiling Floor 09K 12K 18K 929 660 245 841 205 ...
Page 57: ...AUX DC Inverter Free Match 50HZ R32 57 5 Outdoor Unit 5 1 14K 18K 545 800 545 822 315 315 ...
Page 58: ...AUX DC Inverter Free Match 50HZ R32 5 2 21K 27K 834 540 655 854 335 328 ...
Page 59: ...AUX DC Inverter Free Match 50HZ R32 59 5 3 36K 42K 985 675 808 1000 409 395 ...
Page 64: ...AUX DC Inverter Free Match 50HZ R32 3 Ceiling Floor 09k 12k 18k ...
Page 65: ...AUX DC Inverter Free Match 50HZ R32 65 4 Duct 07K 09K 12K 18K ...
Page 67: ...AUX DC Inverter Free Match 50HZ R32 67 5 1 36K 42K ...
Page 73: ...AUX DC Inverter Free Match 50HZ R32 73 Part8 Static pressure curve 1 07K 09K Duct ...
Page 74: ...AUX DC Inverter Free Match 50HZ R32 2 12K Duct ...
Page 75: ...AUX DC Inverter Free Match 50HZ R32 75 3 18K Duct ...
Page 81: ...AUX DC Inverter Free Match 50HZ R32 81 ...
Page 122: ...AUX DC Inverter Free Match 50HZ R32 5 3 2 1 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 ...
Page 135: ...AUX DC Inverter Free Match 50HZ R32 135 2 Cassette 09K 12K 18K ...
Page 139: ...AUX DC Inverter Free Match 50HZ R32 139 4 Duct 4 1 07K 09K 12K ...
Page 141: ...AUX DC Inverter Free Match 50HZ R32 141 4 2 18K ...
Page 143: ...AUX DC Inverter Free Match 50HZ R32 143 5 Outdoor Unit 5 1 14K 18K ...
Page 145: ...AUX DC Inverter Free Match 50HZ R32 145 ...
Page 147: ...AUX DC Inverter Free Match 50HZ R32 147 5 3 36K ...
Page 149: ...AUX DC Inverter Free Match 50HZ R32 149 5 4 42K ...
Page 155: ...AUX DC Inverter Free Match 50HZ R32 155 4 Cassette 4 1 Installation drawing ...
Page 160: ...AUX DC Inverter Free Match 50HZ R32 ...
Page 181: ...AUX DC Inverter Free Match 50HZ R32 181 1 2 21K 27K Main PCB and Driver modular ...
Page 182: ...AUX DC Inverter Free Match 50HZ R32 1 3 36K 42K Main PCB ...
Page 183: ...AUX DC Inverter Free Match 50HZ R32 183 Drive Modular Board ...
Page 184: ...AUX DC Inverter Free Match 50HZ R32 2 Indoor Unit PCB 2 1 09K 12K 18K Cassette ...
Page 185: ...AUX DC Inverter Free Match 50HZ R32 185 2 2 09K 12K 18K Ceilling Floor ...
Page 186: ...AUX DC Inverter Free Match 50HZ R32 2 3 07k 09K 12K 18K Duct ...
Page 191: ...AUX DC Inverter Free Match 50HZ R32 191 Outdoor protection phase sequence ...
Page 193: ...AUX DC Inverter Free Match 50HZ R32 193 2 4 H6 low pressure protection ...
Page 195: ...AUX DC Inverter Free Match 50HZ R32 195 2 5 P5 High exhaust temperature protection ...
Page 196: ...AUX DC Inverter Free Match 50HZ R32 Cooling exhaust temperature protection ...
Page 197: ...AUX DC Inverter Free Match 50HZ R32 197 Heating exhaust temperature protection ...
Page 198: ...AUX DC Inverter Free Match 50HZ R32 2 6 H8 four way valve failure protection ...
Page 199: ...AUX DC Inverter Free Match 50HZ R32 199 2 7 Sensor failure protection ...