100
COMPACT VOICE ALARM SYSTEM
SERVICE MANUAL
12.3.7 DFMS
1
Name
The name field enables assignment of an individual name to the fireman microphone, other than the generic name
assigned by the configurator.
2
Audio Inputs
The
Audio Inputs
field contains all available audio inputs on the DFMS microphone. Item 1 is the microphone used only in
the
Alarm
mode – as the standard setting, the input at Item 1 always has the highest priority of 0 (see the
Priority Manager
tab – the fireman microphone may have priorities assigned from the range 0-99). Item 2 is the same physical microphone as
in Item No 1, however with a General-type priority (200-299). The Item 2 microphone is used to transmit ordinary messages
in the AutroVoice miniVES system, e.g. Public Address. Double-clicking the name of the audio input enables to change the
generic name assigned by the configurator.
3
Logical Inputs
The
Logical Inputs
tab contains all available buttons as well as logical inputs on the fireman microphone. A double click on
the name of a button / logical input enables to change the generic name assigned by the configurator.
4
Events
The
Events
buttons transfers the programmer directly to the
EventConfiguration
tab. This enables to assign any function or
event group to a selected button. A right-click on the name of a button / logical input in the
EventConfiguration
tab, as well
as selection of
Go to definition
, enables to return quickly to the editing menu of the fireman microphone.
5
Mode / Default
The logical input editing window enables activation of the input monitoring function –
Mode
Contact
/
Monitor
. In case the
Monitor
option is selected, it is necessary to install two parametrizing resistors at the end of the line, of 4.7 kΩ.
Summary of Contents for AutroVoice miniVES 2001