2 Modbus Mapping Table
26
© Copyright Reserved Autonics Co., Ltd.
2.4.6
Parameter 4 Setting Group
No(Address)
Parameter Description
Setting range
Factory
default Unit
Note
400251(00FA)
AL
Alarm operation mode
0:
OFF
, 1:
AlD
1
-
400252(00FB)
AlT
Alarm option
0:
AlA
, 1:
AlB
, 2:
AlC
,
3:
AlD
, 4:
AlE
, 5:
AlF
0
-
400253(00FC)
AlH
Alarm high-limit deviation
-F.S to F.S
139
℃
252
℉
400254(00FD)
AlL
Alarm low-limit deviation
-F.S to F.S
139
℃
252
℉
400255(00FE)
aHY
Alarm hysteresis
1
to
5
(
)5
to
%0
)
1
℃
2
to
10
(
@0
to
1)0
)
℉
400256(00FF)
aON
Alarm ON delay time
0
to
60
0
Min
400257(0100)
aOF
Alarm OFF delay time
0
to
60
0
Min
400258(0101)
eAD
External alarm delay time
0
to
60
0
Min
400259(0102)
aN
Alarm output method
0:
NO
, 1:
NC
0
-
400260(0103)
fTY
Evaporation-fan operation
0:
FAN
, 1:
DEF
0
-
400261(0104)
fT
Evaporation-fan control
temperature
-40
to
99
4
℃
-40
to
212
℉
400262(0105)
fHY
Evaporation-fan hysteresis
1
to
5
(
)5
to
%0
)
1
℃
2
to
10
(
@0
to
1)0
)
℉
400263(0106)
FAN
Evaporation-fan mode
0:
EF1
, 1:
EF2
, 2:
EF3
,
3:
EF4
, 4:
EF5
0
-
400264(0107)
pDR
Evaporation-fan start-up
delay time
)00
to
(59
0.00
Min.Sec
400265 to
400300
Reserved
Summary of Contents for TF3 Series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd 1 USER MANUAL For COMMUNICATION ...
Page 2: ...Preface 2 Copyright Reserved Autonics Co Ltd ...
Page 28: ...2 Modbus Mapping Table 28 Copyright Reserved Autonics Co Ltd ...
Page 29: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 29 MCT TF3C1 V1 1 1701US ...