1 Modbus RTU Protocol
© Copyright Reserved Autonics Co., Ltd.
17
1.8
Exception Response-Error Code
When communication error occurs, send response command and transmit exception code after
setting (1) the highest level bit of received command (Function).
Slave Address
(address)
Function
(C8
0 H
Exception Code
Error Check(CRC16)
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
ILLEGAL FUNCTION(Exception Code: 01 H): Not supported command
ILLEGAL DATA ADDRESS(Exception Code: 02 H): Starting address of the requested data
is inconsistent with transmittable address from the device.
ILLRGAL DATA VALUE(Exception Code: 03 H): The requested number of data is
inconsistent with the transmittable number of address.
SLAVE DEVICE FAILURE(Exception Code: 04 H): Not properly complete the requested
command.
The example of reading output stauts (ON: 1, OFF: 0) of Coil 001001(03E8 H) which does not
exist on Slave(Address 17) from Master.
Query (Master)
Slave Address
Function
Starting Address
No. of Points
Error Check
(
CRC16)
High
Low
High
Low
Low
High
11 H
01 H
03 H
E8 H
00 H
01 H
## H
## H
Response (Slave)
Slave Address
Function
(
C80
H
Exception Code
Error Check(CRC16)
Low
High
11 H
81 H
02 H
## H
## H
CRC16
Summary of Contents for TF3 Series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd 1 USER MANUAL For COMMUNICATION ...
Page 2: ...Preface 2 Copyright Reserved Autonics Co Ltd ...
Page 28: ...2 Modbus Mapping Table 28 Copyright Reserved Autonics Co Ltd ...
Page 29: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 29 MCT TF3C1 V1 1 1701US ...