J-239
Temperature Transmitters with HART Protocol
•
Follow instructions in 'Cautions during Use'.
Otherwise, it may cause unexpected accidents.
•
Power supply should be insulated and limited voltage/current or Class 2, SELV power
supply device.
•
Keep away from high voltage lines or power lines to prevent inductive noise.
Do not use near the equipment which generates strong magnetic force or high frequency noise.
•
Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
•
The explosion-proof standard of this unit is Ex d IIC T6, protection structure of this unit is
IP67 and the range of max. surface temperature is below 85
℃
.
Use the verified explosion-proof electric connection (cable gland or sealing fitting)
•
This unit may be used in the following environments.
①
Indoors (in the environment condition rated in 'Specifications')
②
Altitude max. 2,000m
③
Pollution degree 2
④
installation Category II
The explosion-proof unit is certified and the same specifications which is reported to Korea Gas Safety Cor
-
poration. (This unit is manufactured following by the announcement 2013-54 of Ministry of Employment and
Labor of Korea.)
Cautions During Use
1. PV LRV
2. URV
HELP
HOME
②
Select
'1. PV LRV'
(Low temperature range) and
press the
key.
PV LRV
0.000 deg C
0.000
HELP
DEL
ESC
ENTER
③
Set Low temperature range and press the
(F4)
key.
1. PV LRV
2. URV
HELP
HOME
④
Select
'2. URV'
(High temperature range) and press the
key.
Online (Generic)
1. Device Setup
2. PV
3. PV Ao
4. PV LRV
5. URV
SAVE
①
Press the key for 3 sec. Select the
'4. PV LRV'
by
,
keys and press the
key.
PV URV
100.000 deg C
100.000
HELP
DEL
ESC
ENTER
⑤
Set High temperature range and press the
(F4)
key.
1. PV LRV 0.000 deg C
2. URV 100.000 deg C
HELP
SEND
HOME
⑥
When the set temperature range is correct,
press the
(F2) key.
- WARNING -
Pressing ' OK ' will
change device output
put 100P in manual
⑦
Press the
(F4) key.
- WARNING -
Return control 100P
To automatic control
O K
⑧
Press the
(F4) key.
1. PV LRV 0.000 deg C
2. URV 100.000 deg C
HELP
HOME
⑨
Check the set temperature range. Press the
(F3)
key. HART communication is OFF.
Connect a HART communicator and set temperature range as below by a HART communicator.
Temperature Range Setting
Proper Usage