J-239

Temperature Transmitters with HART Protocol

 

Follow instructions in 'Cautions during Use'.

 

Otherwise, it may cause unexpected accidents.

 

Power supply should be insulated and limited voltage/current or Class 2, SELV power 

 

supply device.

 

Keep away from high voltage lines or power lines to prevent inductive noise. 

Do not use near the equipment which generates strong magnetic force or high frequency noise.

 

Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.

 

 The explosion-proof standard of this unit is Ex d IIC T6, protection structure of this unit is

 

IP67 and the range of max. surface temperature is below 85

Use the verified explosion-proof electric connection (cable gland or sealing fitting)

 

This unit may be used in the following environments. 

Indoors (in the environment condition rated in 'Specifications')

 

Altitude max. 2,000m 

Pollution degree 2 

installation Category II

   

  The explosion-proof unit is certified and the same specifications which is reported to Korea Gas Safety Cor

-

poration. (This unit is manufactured following by the announcement 2013-54 of Ministry of Employment and 

Labor of Korea.)

 

Cautions During Use

1. PV LRV

2. URV

HELP

HOME

 Select 

'1. PV LRV'

(Low temperature range) and 

    press the 

  key. 

   PV LRV

   0.000 deg C

0.000

HELP

DEL

ESC

ENTER

 Set Low temperature range and press the 

 (F4) 

key.

1. PV LRV

2. URV

HELP

HOME

 Select 

'2. URV'

(High temperature range) and press the 

 key. 

Online (Generic)

1. Device Setup

2. PV

3. PV Ao

4. PV LRV

5. URV   

SAVE

 Press the   key for 3 sec. Select the 

'4. PV LRV'  

by  

 

 keys and press the 

 key.

   PV URV

   100.000 deg C

   100.000

HELP

DEL

ESC

ENTER

 Set High temperature range and press the 

 (F4) 

key. 

1. PV LRV 0.000 deg C

2. URV 100.000 deg C

HELP

SEND

HOME

 When the set temperature range is correct, 

     press the 

 (F2) key. 

                 - WARNING -

           Pressing ' OK ' will

           change device output

           put 100P in manual

  Press the 

 (F4) key. 

                 - WARNING -

           Return control 100P

           To automatic control

O K

  Press the 

 (F4) key. 

1. PV LRV 0.000 deg C

2. URV 100.000 deg C

HELP

HOME

 Check the set temperature range. Press the 

 (F3) 

key. HART communication is OFF.

Connect a HART communicator and set temperature range as below by a HART communicator.

 Temperature Range Setting

 Proper Usage

Summary of Contents for KT-502H Series

Page 1: ...500mV 100 2000mV Output DC4 20mA 2 wire Accuracy 0 3 Alarm Below 3 8mA Over 20 5mA Sensor break 3 6mA Load Max V power supply 7 5V 0 22A Galvanic insulation 2 000VAC input output Environ ment Ambient temperature 20 to 70 storage 20 to 80 Ambient humidity 0 to 85 RH storage 0 to 85 RH Explosion class 1 Ex d IIC T6 Protection structure IP67 IEC standard Material Body Aluminum AlDc 8S Cover O Ring Bu...

Page 2: ...000 454 to 1832 J Fe CuNi 210 to 1200 346 to 2192 K NiCr Ni 270 to 1372 454 to 2501 6 N NiCrSi NiSi 270 to 1300 454 to 2372 R PtRh13 Pt 50 to 1768 58 to 3214 4 S PtRh10 Pt 50 to 1768 58 to 3214 4 T Cu CuNi 270 to 400 454 to 752 Analog Voltage 10 75mV 100 100mV 100 500mV 100 2000mV Opening cover To open the cover unscrew the M3 6L headless bolt using a 1 5 hexagon wrench and rotate the cover Ø83 14...

Page 3: ...NTER Enter meter Value 4 000 HELP DEL ABORT ENTER Setting fid dev output to 4mA ABORT O K WARN Loop should be removed from automatic control ABORT O K Select the 1 Device Setup by keys and press the key Connect a HART communicator and adjust current trim as below by a HART communicator Select the 2 Diag Service by keys and press the key Select the 4 D A trim by keys and press the key Press the F4 ...

Page 4: ...fications which is reported to Korea Gas Safety Cor poration This unit is manufactured following by the announcement 2013 54 of Ministry of Employment and Labor of Korea Cautions During Use 1 PV LRV 2 URV HELP HOME Select 1 PV LRV Low temperature range and press the key PV LRV 0 000 deg C 0 000 HELP DEL ESC ENTER Set Low temperature range and press the F4 key 1 PV LRV 2 URV HELP HOME Select 2 URV ...

Reviews: