U-12

KRN1000 Series

-|Transparent setting guide|-

 Special Function

It displays the applied measuring value of the set special 

function. Depending on Input type, applied special function is 

different.

 

 Setting range :

  -  When input type is temperature sensor (thermocouple, 

RTD): None ↔ Difference

  -  When input type is analog (voltage, current (shunt)): 

Linear ↔ Root ↔ Square ↔ Two Unit

     Two Unit is displayed when input type is set as 4-20mA 

(shunt).

It is available to set when input type is temperature sensor 

(thermocouple, RTD). It displays the deviation of reference 

channel measuring value. 

(Display value = standard channel measuring value - 

reference channel measuring value)

 

The set channel as analog (voltage, current (shunt)) of 

Input type is not able to set as reference channel.

 

 If there is no set reference channel, it displays standard 

channel measuring value.

 

If any one of reference channel, or standard channel is 

break (BURN), high-limit value (HHHH), low-limit value 

(LLLL) status, it displays as correspond value. If you 

select the channel which is used Difference function 

as reference channel, it displays the value based on 

calculating actual measuring value, not display value of 

reference channel.

In case of voltage, current (shunt) input type, this mode 

is used when input value is calculated by square for the 

desired display value. Reverse of Root, flux signal is 

calculated by square for differential pressure signal.

E.g.)In case low-limit range: -5V, high-limit range: +5V and 

in case low-limit scale: -1000, high-limit scale: 1000, if 

input value is 2V, display value is -20.

It applies low-limit scale and high-limit scale to low-limit 

input value and high-limit input value and displays this 

values. 

E.g.)In case low-limit input value: -5V, high-limit input value: 

+5V and in case low-limit scale: -1000, high-limit scale: 

1000, if input value is 2V, display value is 400.

In case voltage, current (shunt) input type, this mode 

is used when input value is calculated by Root ( ) for 

the desired display value. Differential pressure signal of 

differential pressure flow meter is calculated Root (

)

for the to-be measured flux. This function is used to 

measure flux by input value.

E.g.)In case low-limit input value: -5V, high-limit input value: 

+5V and in case low-limit scale: -1000, high-limit scale: 

1000, if input value is 2V, display value is approx. 

673.32.

For compound pressure, if input pressure is lower than 

atmospheric pressure (0), it displays the degree of a 

vacuum with mmHg unit. If input pressure is higher than 

or same as atmospheric pressure (0), it displays positive 

pressure with  kg/cm

2

 unit.

When using Two Unit function, low-limit value is fixed as 

-760mmHg and kg/cm

value is able to set within Setting 

range 1 to 35.

Two Unit limits scale point as  0 ↔ 0.0 ↔ 0.00 . When 

using Two Unit, display unit is automatically changed as 

mmHg or kg/cm

2

.

This function has two different unit values and it is 

impossible to calculate by recording method and digital filter 

and ignore it. 

E.g.)  If pressure range is -760mmHg to 3kg/cm

2

, and 

pressure transmitter outputs 4-20mA, for 4mA input it 

displays -760mmHg, 8mA input is unit changing point. 

For 20mA input, it displays 3kg/cm

2

.

 Functions

 History

 

Linear

 

Root

 

Square

 

Two Unit

 

Difference (deviation)

It checks data history which is recording at [Menu]-
[Display]-[History]. When recording is stop, it displays 
warning message. 

 

Checks data history by each group, channel.

 

Data history displays as horizontal/vertical trend, divided 
horizontal/vertical trend. 

 

Saves the screen as *.bmp file. 

It checks the saved data history at internal/external 
memory. 
Touch [Menu]-[Display]-[File History]. 

 

Set the information of display group or channel. 

 

Data history displays as horizontal/vertical trend, divided 
horizontal/vertical trend. 

 File History

Summary of Contents for KRN1000 Series

Page 1: ...unication Visit our website www autonics com to download the manuals The user manual includes product specifications functions and operations The user manual for communication includes information about Modbus RTU protocol Modbus TCP protocol and Modbus mapping table LCD Touchscreen Paperless Recorder Features Manuals Comprehensive Device Management Program DAQMaster DAQMaster is comprehensive dev...

Page 2: ...mpling period 1 to 4 CH 25ms 125ms 250ms 5 to 16 CH 125ms 250ms internal sampling period is average movement filter and alarm output operation unit time Recording period 1 to 3600 sec Internal memory Approx 200MB External memory 2 SD USB memory max 32GB Dielectric strength 2300VAC 50 60Hz for 1 min between power terminals and case Except Ethernet and USB device Vibration Mechanical 10 to 60Hz 4 9m...

Page 3: ...ed at the same time If sensor input line is longer it is recommended to use shield cable to reduce noise Type Input Output type Description Universal input Input type RTD JPt100Ω DPt100Ω DPt50Ω Cu100Ω Cu50Ω supplied current approx 190µA Thermocouple B C W5 E G J K L L Russia N P R S T U Analog Voltage 60mV 200mV 2V 1 5V 5V 1V 10V Current 0 20mA 4 20mA measurable when using 250Ω shunt resistance 1 ...

Page 4: ...0 0 32 0 to 1112 0 273 2 to 873 2 U CC TC U 200 0 to 400 0 328 0 to 752 0 73 2 to 673 2 Platinel Ⅱ TC P 0 0 to 1350 0 32 0 to 2462 0 273 2 to 1623 2 RTD Cu50Ω CU50 200 0 to 200 0 328 0 to 392 0 73 2 to 473 2 Cu100Ω CU100 200 0 to 200 0 328 0 to 392 0 73 2 to 473 2 JPt100Ω JPT100 200 0 to 600 0 328 0 to 1112 0 73 2 to 873 2 DPt50Ω DPT50 200 0 to 600 0 328 0 to 1112 0 73 2 to 873 2 DPt100Ω DPT100 20...

Page 5: ...nput output Power input Power connection 100 240VAC 50 60Hz Universal input Communication output Option input output 1 Option input output 2 Alarm output 8 channels Alarm output 6 channels Digital input 2 channels Option input output 3 Option input output 4 Alarm output 6 channels Power for transmitter output Alarm output 4 channels Digital input 2 channels Power for transmitter output In case of ...

Page 6: ...digital figures Front cover Open the front cover There are power switch and USB Host Device SD card slot Power switch Turn ON OFF the power of KRN1000 USB host port Connect the USB memory It recognizes up to 32GB When using extension cable cable length should be up to 1 5m Connect only USB device USB device port Used for connecting PC via Modbus RTU communication SD card slot SD card memory slot I...

Page 7: ...t value display part Displays the measured value of each channel as graph Set one graph among 9 graphs bar graph Vertical Horizontal Trend graph Vertical Horizontal Mixed graph Divided Vertical Horizontal Trend Graph Group All Digital Bar graph Vertical Horizontal Trend graph Divided Vertical Horizontal Trend Graph Vertical Horizontal Mixed graph Group All Digital Screen Description ...

Page 8: ...U 11 LCD Touchscreen Paperless Recorder Transparent setting guide Touch the status display part at the upper screen and menu appears as right screen Menu is as below Menu ...

Page 9: ... limit scale 1000 high limit scale 1000 if input value is 2V display value is 400 In case voltage current shunt input type this mode is used when input value is calculated by Root for the desired display value Differential pressure signal of differential pressure flow meter is calculated Root for the to be measured flux This function is used to measure flux by input value E g In case low limit inp...

Page 10: ...Set the summer time duration Set enable to summer time and designate start date and end date of summer time at Menu System Info Date Time High Low Limit Graph Scale Value In case of temperature sensor input thermocouple RTD set the graph scale value to set the desired record range Therefore it helps to record as curve at the desired range Display Scale For analog input this function is to set 9999...

Page 11: ...network hub HUB and gateway etc there is no distance limit but it is recommended to use min network Please use communication cables which is satisfied the below conditions RS422 485 communication Shield Twist Pair over AWG24 characteristic impedance 100Ω capacity component 50 pF m cable length max 1km Ethernet communication Over CAT5E cable max length 100m USB communication Single cable built in f...

Page 12: ... When input type is temperature sensor Thermocouple RTD and input is break it flashes BURN It is cleared when input is connected ASKey When forgetting and entering invalid password 3 times ASKey appears with error message Contact our service center with ASKey Functions Factory Default Display Menu Default History Mode Graph H Trend Memory Internal Memory File Name Parameter Default Parameter Defau...

Page 13: ...0 Internal Memory Storage Options Overwrite System Info Parameter Default Parameter Default Date Setting Auto set Summer Time Disable Time Setting Summer Time Duration 1month 1day to 1month 1day Date Type yyyy mm dd Time 1 hour Parameter Default Parameter Default Reservation Recording Date Reservation Type Disable Reservation Recording Time Parameter Default Parameter Default Device Name KRN1000 R...

Page 14: ...same thickness and length For thermocouple CT temperature sensor use the designated compensation wire for extending wire Keep away from high voltage lines or power lines to prevent inductive noise In case installing power line and input signal line closely use line filter or varistor at power line and shielded wire at input signal line Do not use near the equipment which generates strong magnetic ...

Reviews: