3 Modbus Mapping Table
78
© Copyright Reserved Autonics Co., Ltd.
3.4.5
RECORD SETUP(Record setting
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
401551 (060E) 03/06/16 R/W Record Mode
Record mode
0:Graph, 1:Digital
-
Graph
401552 (060F) 03/06/16 R/W Digital Print Type 1 line record channel
during numeric recording 0:OneCH, 1:TwoCH
-
TwoCH Enables only in
Digital mode
401553 (0610) 03/06/16 R/W Standard Speed Standard record speed 0:10, 1:20, 2:40, 3:60,
4:120, 5:240,
mm/h 20
Enables only in
Graph mode.
In Digital mode,
it is exception
process.
When changing
standard record
speed, option
and alarm record
speed is also
changed as
same value.
Option and
alarm record
speed cannot be
lower than
standard record
speed.
401554 (0611) 03/06/16 R/W Option Speed
Option record speed
0:10, 1:20, 2:40, 3:60,
4:120, 5:240,
mm/h 20
401555 (0612) 03/06/16 R/W Memo Period
Digital memo period
Refer to 8.5.5 Digital
Memo Period of
KRN100 user manual.
(Depending on the
number of input
channel.)
0:1min 1:5min 2:10min
3:15min 4:30min
5:hour 6:2hour 7:3hour
8:4hour 9:hour
10:16hour 11:24hour
min
Refer to
the table
of 9-6-1-
1-3.
(Dependi
ng on
the
number
of input
channel.
)
Enables only in
Graph mode.
In Digital mode,
it is exception
process.
Depending on
the number of
printed channel,
min. set value is
changed.
401556 (0613) 03/06/16 R/W Divide Zone
Record zone division
None:1
2 to 12
Zone None
Enables only in
Graph mode.
In Digital mode,
it is exception
process.
401557 (0614) 03/06/16 R/W Standard Period Standard record period
00m00s to 99m59s
Refer to 8.5.7
Standard Period and
8.5.8 Option Period of
KRN100 user manual.
(Depending on the
number of input
channel.)
-
20m00s
Enables only in
Graph mode.
In Digital mode,
it is exception
process.
Enables to set
with second unit.
For example, to
set 10 min. 10
sec., set 610
which is
10min.×60sec.×
10sec.
Depending on
the number of
printed channel,
there limit to min.
set value.
401558 (0615) 03/06/16 R/W Option Period
Option record period
-
20m00s
401559 (0616) 03/06/16 R/W Listing Language Language for list output 0: English , 1: Korea -
English
401560 (0617) 03/06/16 R/W Alarm Speed
Alarm record speed
0:10, 1:20, 2:40, 3:60,
4:120, 5:240
mm/h 20
Enables only in
Graph mode.
In Digital mode,
it is exception
process.
When changing
standard record
speed, option
and alarm record
speed is also
changed as
same value.
Option and
alarm record
Summary of Contents for krn100 series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Page 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Page 82: ......