Functions

  

■ Single-turn data reset

The single-turn data will be initialized to 0 when 0 - 1 VDCᜡ (min. 100 ms) is applied to single-

turn data reset cable. 

Connect the line to OPEN or +V in case of not using single-turn data reset cable.

  

Multi-turn count reset

The multi-turn count will be initialized to 0 when 0 - 1 VDCᜡ (min. 100 ms) is applied to multi-

turn count reset cable.

 

Connect the line to OPEN or +V in case of not using multi-turn count reset cable. 

If Overflow alarm (OVF) occurs, Overflow alarm (OVF) will be initialized when multi-turn count 

reset is applied.

  

Direction

If the power is ON after connecting the direction cable to OPEN or +V, the output increases 

when rotating direction is CW based on facing the shaft, and if the power is ON after connecting 

to 0 - 1 VDCᜡ (min. 100 ms), the output increases when rotating direction is CCW based on 

facing the shaft. 

Since the direction setting is initial setting which is set with power ON, if the setting value is 

changed, both single-turn data and multi-turn count will be initialized to 0.

  

Clear

Both single-turn data and multi-turn count will be initialized to 0 when 0 - 1 VDCᜡ (min. 100 

ms) is applied to Clear cable. 

Connect the line to OPEN or +V in case of not using Clear cable. 

If Overflow alarm (OVF) occurs, Overflow alarm (OVF) will be initialized when Clear is applied.

  

Latch

•  Parallel NPN open collector output model only

The single-turn data, multi-turn count and overflow output will be remaind its value at latch 

point when 0 - 1 VDCᜡ (min. 100 ms) is applied to Latch cable. 

If Latch cable is connected to OPEN or +V, output will return to operating encoder output.

  

■ Overflow alarm (OVF)

Occurs when multi-turn count is out of counting range (0 to 8191 revolution). 

If the direction setting is changed or multi-turn count reset, clear is applied, the overflow alarm 

will be initialized.