-|Transparent Guide|-

Parameter

Display

Defaults

Setting range

Display 

condition

P1-29 Input special 

function

InSF

LIN

LIN: output the input value, 

ROOT: output the square root of the 

input value, 

SQAR: output the square of the input 

value, 

TUF: Two Unit Function 

 01)

P1-1 Input 

type: 

Analog

P1-30 Atmospheric 

pressure

)PSI

0*00

Low-limit to high-limit input value

P1-1 Input 

type: Analog

&

P1-29 Input 

special 

function: 

TUF

P1-31 Span 

correction

SPAN

!000

0.900 to 1.100

P1-1 Input 

type: 

Analog

&

P1-37 

User level: 

HIGH

P1-32

Normal 

average 

digital filter

AvF

01

01 (OFF) to 16

P1-37 

User level: 

HIGH

P1-33

Moving 

average 

digital filter

MAvF

04

P1-34 Digital input 

key 

DI-K

HOLD

HOLD: hold display value, 

ZERO: remote zero, AL.RE: alarm reset

 02)

•  Press the [◀] + [▲] keys for 3 sec to 

operates with the set function.

 

-

P1-35 Display part 

color 

 03)

COLR

GRN

GRN: green / green, 

YELO: yellow / yellow, RED: red / red, 

R--G: red / green, G--R: green / red

• Display: normal / error occur

-

P1-36

Sensor 

disconnection 

alarm output

BURN

ON

ON, OFF

•  Refer to the error.

P1-1 Input 

type: Temp. 

sensor

P1-37 User level

USER

STND

STND, HIGH

-

P1-38 Lock

LOCK

OFF

OFF:  program / monitoring mode -

 

enable to check and setting

LOC1

:  program

 

mode - enable to check,

 

monitoring mode -  enable to check 

and setting

LOC2

:   program

 

mode  -  disable to check and

 

setting,

  

monitoring mode - enable to check

-

 01)  Pressure of pressure sensor < atmospheric pressure: display of vacuum degree in mmHg unit

 

Pressure of pressure sensor > atmospheric pressure: display of positive pressure in kg/cm

2

 02)  In the alarm output model, AL.RE displayed when the setting value of P1-21, 23, 25, 27 Alarm1 ~ 4 options are 

alarm latch or alarm latch and standby sequence.

 03)  The color of the display part in monitoring mode and program mode is red.

  

Pulse

 input

Parameter

Display

Defaults

Setting range

Display 

condition

P2-1 Input type

IN-P

50KH

• 

Refer to Input Type and Range

-

P2-2 Display unit

dUNT

KHZ

kHz, Hz, %, OFF

-

P2-3 Low-limit 

input value

L-RG

0)00

Within input type range

•  Low-limit input value + 20 % F.S. <

 

High-limit input value

-

P2-4 High-limit 

input value

H-RG

5)00

P2-5

Decimal 

point 

position

dP

)00

0.0, 0.00, 0.000, 0

• 

Set the decimal point position of the 

high / low-limit scale.

-

P2-6 Low-limit scale

L-SC

0)00

-1999 to 9999

-

P2-7 High-limit scale

H-SC

5)00

P2-8 Input correction

IN-B

000

-999 to 999

-

P2-9

Low-limit 

value of 

transmission 

output 1

lOR1

0$00

[

Transmission (DC 0 - 20 mA) output model]

DC 0 - 20 mA

-

0)00

[

Transmission (0 - 10 VDCᜡ) output model]

0 - 10 VDCᜡ

P2-10

High-limit 

value of 

transmission 

output 1

hOR1

2)00

[

Transmission (DC 0 - 20 mA) output model]

DC 0 - 20 mA

-

1)00

[

Transmission (0 - 10 VDCᜡ) output model]

0 - 10 VDCᜡ

P2-11

Low-limit 

value of 

transmission 

output 2

lOR2

0$00

[

Transmission (DC 0 - 20 mA) output model]

DC 0 - 20 mA

-

0)00

[

Transmission (0 - 10 VDCᜡ) output model]

0 - 10 VDCᜡ

P2-12

High-limit 

value of 

transmission 

output 2

hOR2

2)00

[

Transmission (DC 0 - 20 mA) output model]

DC 0 - 20 mA

-

1)00

[

Transmission (0 - 10 VDCᜡ) output model]

0 - 10 VDCᜡ

P2-13 Bar display 

CH

BAR

OUT1

[

Transmission output model]

OUT1, OUT2

P2-32 User

 

level: HIGH

P2-14

Low-limit 

scale value of 

transmission 

output 1

lOU1

0)00

[

Transmission output model]

Low-limit

 to 

high-limit

 scale

-

P2-15

High-limit 

scale value of 

transmission 

output 1

hOU1

5)00

P2-16

Low-limit 

scale value of 

transmission 

output 2

lOU2

0)00

P2-17

High-limit 

scale value of 

transmission 

output 2

hOU2

5)00

P2-18

Input and 

transmission 

output 

extension

ExIO

5P

[

Transmission output model]

5P:  output DC 3.2 - 20.8 mA, 0 - 10.5 VDCᜡ 

out of 5 % of analog input range

10P:   output DC 2.4 - 21.6 mA, 0 - 11 VDCᜡ 

out of 10 % of analog input range

0P:  output DC 4 - 20 mA, 0 - 10 VDCᜡ in 

the analog input range

P2-32 User

 

level: HIGH

P2-19 Alarm 1 

operation

AL-1

AT!A

□□□.■

[Alarm output model] □□□

AT1: high-limit alarm, AT2: low-limit

 

alarm, SBA: sensor break alarm, AT0: 

no alarm output

-

P2-20 Alarm 1 option

[Alarm output model] ■

A: standard alarm, B: alarm 

latch

C: standby sequence, 

D: alarm latch and standby sequence

• 

Enter alarm option setting mode

 

:  Operate in ‘Alarm 1 operation’ mode 

select AT1 or AT2 and input [◀] key

-

P2-21 Alarm 2 

operation

AL-2

AT@A

□□□.■ [Alarm output model]

Same as ‘P2-19 / 20 Alarm 1 operation 

/ option’ 

• 

Depending on the number of alarm 

outputs, whether to display alarm 3 / 

4 is different.

-

P2-22 Alarm 2 option
P2-23 Alarm 3 

operation

AL-3

AT!A

□□□.■

P2-24 Alarm 3 option
P2-25 Alarm 4 

operation

AL-4

AT@A

□□□.■

P2-26 Alarm 4 option

P2-27 Alarm output 

hysteresis

A-HY

001

[Alarm output model]

001 to 999

P2-19 to 26

Alarm 

operation

 

/ option: 

AT1.A, 

AT2.A

P2-28 Span 

correction

SPAN

!000

0.900 to 1.100

P2-32 User

 

level: HIGH

P2-29

Moving 

average 

digital filter

MAvF

04

01 (OFF) to 16

P2-30 Digital input 

key 

DI-K

HOLD

HOLD: hold display value, 

ZERO: remote zero, AL.RE: alarm reset

 01)

•  Press the [◀] + [▲] keys for 3 sec to 

operates with the set function.

 

-

P2-31 Display part 

color

COLR

GRN

GRN: green / green, 

YELO: yellow / yellow, RED: red / red, 

R--G: red / green, G--R: green / red

• Display: normal / error occur

-

P2-32 User level

USER

STND

STND, HIGH

-

P2-33 Lock

LOCK

OFF

OFF:  program / monitoring mode -

 

enable to check and setting

LOC1

:  program

 

mode - enable to check,

 

monitoring mode -  enable to check 

and setting

LOC2

:   program

 

mode  -  disable to check and

 

setting,

  

monitoring mode - enable to check

-

 01) It can be applied when the setting value of the alarm option is alarm latch or alarm latch and standby sequence.