-|Transparent Guide|-
Parameter
Display
Defaults
Setting range
Display
condition
P1-29 Input special
function
InSF
LIN
LIN: output the input value,
ROOT: output the square root of the
input value,
SQAR: output the square of the input
value,
TUF: Two Unit Function
01)
P1-1 Input
type:
Analog
P1-30 Atmospheric
pressure
)PSI
0*00
Low-limit to high-limit input value
P1-1 Input
type: Analog
&
P1-29 Input
special
function:
TUF
P1-31 Span
correction
SPAN
!000
0.900 to 1.100
P1-1 Input
type:
Analog
&
P1-37
User level:
HIGH
P1-32
Normal
average
digital filter
AvF
01
01 (OFF) to 16
P1-37
User level:
HIGH
P1-33
Moving
average
digital filter
MAvF
04
P1-34 Digital input
key
DI-K
HOLD
HOLD: hold display value,
ZERO: remote zero, AL.RE: alarm reset
02)
• Press the [◀] + [▲] keys for 3 sec to
operates with the set function.
-
P1-35 Display part
color
03)
COLR
GRN
GRN: green / green,
YELO: yellow / yellow, RED: red / red,
R--G: red / green, G--R: green / red
• Display: normal / error occur
-
P1-36
Sensor
disconnection
alarm output
BURN
ON
ON, OFF
• Refer to the error.
P1-1 Input
type: Temp.
sensor
P1-37 User level
USER
STND
STND, HIGH
-
P1-38 Lock
LOCK
OFF
OFF: program / monitoring mode -
enable to check and setting
LOC1
: program
mode - enable to check,
monitoring mode - enable to check
and setting
LOC2
: program
mode - disable to check and
setting,
monitoring mode - enable to check
-
01) Pressure of pressure sensor < atmospheric pressure: display of vacuum degree in mmHg unit
Pressure of pressure sensor > atmospheric pressure: display of positive pressure in kg/cm
2
02) In the alarm output model, AL.RE displayed when the setting value of P1-21, 23, 25, 27 Alarm1 ~ 4 options are
alarm latch or alarm latch and standby sequence.
03) The color of the display part in monitoring mode and program mode is red.
■
Pulse
input
Parameter
Display
Defaults
Setting range
Display
condition
P2-1 Input type
IN-P
50KH
•
Refer to Input Type and Range
-
P2-2 Display unit
dUNT
KHZ
kHz, Hz, %, OFF
-
P2-3 Low-limit
input value
L-RG
0)00
Within input type range
• Low-limit input value + 20 % F.S. <
High-limit input value
-
P2-4 High-limit
input value
H-RG
5)00
P2-5
Decimal
point
position
dP
)00
0.0, 0.00, 0.000, 0
•
Set the decimal point position of the
high / low-limit scale.
-
P2-6 Low-limit scale
L-SC
0)00
-1999 to 9999
-
P2-7 High-limit scale
H-SC
5)00
P2-8 Input correction
IN-B
000
-999 to 999
-
P2-9
Low-limit
value of
transmission
output 1
lOR1
0$00
[
Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
-
0)00
[
Transmission (0 - 10 VDCᜡ) output model]
0 - 10 VDCᜡ
P2-10
High-limit
value of
transmission
output 1
hOR1
2)00
[
Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
-
1)00
[
Transmission (0 - 10 VDCᜡ) output model]
0 - 10 VDCᜡ
P2-11
Low-limit
value of
transmission
output 2
lOR2
0$00
[
Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
-
0)00
[
Transmission (0 - 10 VDCᜡ) output model]
0 - 10 VDCᜡ
P2-12
High-limit
value of
transmission
output 2
hOR2
2)00
[
Transmission (DC 0 - 20 mA) output model]
DC 0 - 20 mA
-
1)00
[
Transmission (0 - 10 VDCᜡ) output model]
0 - 10 VDCᜡ
P2-13 Bar display
CH
BAR
OUT1
[
Transmission output model]
OUT1, OUT2
P2-32 User
level: HIGH
P2-14
Low-limit
scale value of
transmission
output 1
lOU1
0)00
[
Transmission output model]
Low-limit
to
high-limit
scale
-
P2-15
High-limit
scale value of
transmission
output 1
hOU1
5)00
P2-16
Low-limit
scale value of
transmission
output 2
lOU2
0)00
P2-17
High-limit
scale value of
transmission
output 2
hOU2
5)00
P2-18
Input and
transmission
output
extension
ExIO
5P
[
Transmission output model]
5P: output DC 3.2 - 20.8 mA, 0 - 10.5 VDCᜡ
out of 5 % of analog input range
10P: output DC 2.4 - 21.6 mA, 0 - 11 VDCᜡ
out of 10 % of analog input range
0P: output DC 4 - 20 mA, 0 - 10 VDCᜡ in
the analog input range
P2-32 User
level: HIGH
P2-19 Alarm 1
operation
AL-1
AT!A
□□□.■
[Alarm output model] □□□
AT1: high-limit alarm, AT2: low-limit
alarm, SBA: sensor break alarm, AT0:
no alarm output
-
P2-20 Alarm 1 option
[Alarm output model] ■
A: standard alarm, B: alarm
latch
,
C: standby sequence,
D: alarm latch and standby sequence
•
Enter alarm option setting mode
: Operate in ‘Alarm 1 operation’ mode
select AT1 or AT2 and input [◀] key
-
P2-21 Alarm 2
operation
AL-2
AT@A
□□□.■ [Alarm output model]
Same as ‘P2-19 / 20 Alarm 1 operation
/ option’
•
Depending on the number of alarm
outputs, whether to display alarm 3 /
4 is different.
-
P2-22 Alarm 2 option
P2-23 Alarm 3
operation
AL-3
AT!A
□□□.■
P2-24 Alarm 3 option
P2-25 Alarm 4
operation
AL-4
AT@A
□□□.■
P2-26 Alarm 4 option
P2-27 Alarm output
hysteresis
A-HY
001
[Alarm output model]
001 to 999
P2-19 to 26
Alarm
operation
/ option:
AT1.A,
AT2.A
P2-28 Span
correction
SPAN
!000
0.900 to 1.100
P2-32 User
level: HIGH
P2-29
Moving
average
digital filter
MAvF
04
01 (OFF) to 16
P2-30 Digital input
key
DI-K
HOLD
HOLD: hold display value,
ZERO: remote zero, AL.RE: alarm reset
01)
• Press the [◀] + [▲] keys for 3 sec to
operates with the set function.
-
P2-31 Display part
color
COLR
GRN
GRN: green / green,
YELO: yellow / yellow, RED: red / red,
R--G: red / green, G--R: green / red
• Display: normal / error occur
-
P2-32 User level
USER
STND
STND, HIGH
-
P2-33 Lock
LOCK
OFF
OFF: program / monitoring mode -
enable to check and setting
LOC1
: program
mode - enable to check,
monitoring mode - enable to check
and setting
LOC2
: program
mode - disable to check and
setting,
monitoring mode - enable to check
-
01) It can be applied when the setting value of the alarm option is alarm latch or alarm latch and standby sequence.