4 Temperature input module [ARIO-S-AI-TC/RTD]
24
© Copyright Reserved Autonics Co., Ltd.
Type
Temperature input module
Insulation resistance
100M
Ω
(at 500VDC
ᜡ
megger), I/O to inner circuit: photocoupler insulated
Dielectric strength
1000VAC
ᜠ
50/60Hz for 1 min
Noise immunity
±
500VDC
ᜡ
the square wave noise (pulse width: 1
㎲
) by the noise simulator
Vibration
0.7mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour
Vibration (malfunction)
0.5mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 min.
Shock
300m/s
²
(approx. 30G) in each X, Y, Z direction for 3 times
Shock (malfunction)
100m/s
²
(approx. 10G) in each X, Y, Z direction for 3 times
Ambient temperature
-10 to 55
℃
, storage: -25 to 70
℃
(a non-freezing or condensation environment)
Ambient humidity
35 to 85%RH, storage: 35 to 85%RH (a non-freezing or condensation environment)
Protection structure
IP20 (IEC standards)
Material
Terminal: polyamide6, Body: modified polyphenylene oxide,
Base: polyamide6, poly oxy methylene
Approval
Weight (packaging)
Approx. 75g ( approx. 108g )
※1.
At room temperature (23℃ ± 5℃)
▪ Below -100℃ of TC K, J, T, N, E and TC L, U, PLII: ±4℃ ±1 digit
▪ Below ±200℃ of TC R, S: ±4℃ ±1 digit
▪ Below 400℃ of TC B: No display accuracy
▪ RTD Cu 50 Ω / 100 Ω, Ni 100 Ω / 120 Ω / 1000 Ω: ±2℃ ±1digit
Out of room temperature range
▪ TC: (±0.5% F.S or ±7℃, select the higher one) ± 1digit
▪ RTD: (±0.5% F.S or ±3℃, select the higher one) ±1digit
※
Power supply is from I/O power of coupler or ARIO-P-F Series. Normal operation is available when I/O power voltage is supplied.
For connecting the modules, consider power concumption of the sensors and drivers connected the ARIO coupler and power
modules.In case of one coupler connecting, the ARIO analog module is available to connect up to 4 units.