Parity Options: NONE, EVEN, ODD.
Default Parity : EVEN
Note that if parity is set to ODD or EVEN, Stop Bits will be set
to 1 and cannot be changed.
From the Set-up menu, Use and to select the
Parity options.
Long Press to enter the selection routine.
The Parity setting will flash. Use and to choose
Parity.
Parity
Example shows:
Set Parity: EVEN
And long press for confirmation.
Press to return the main set up menu.
Baud rate options: 2400 4800 9600 19200 38400 (bps).
Default: 9600bps
From the Set-up menu, Use and to select the
Baud rate options.
Long press to enter the selection routine.
The Baud Rate setting will flash. Use and to
choose Baud Rate.
Long press for confirmation and then press to
return to the main menu.
Baud rate
Product development is continuous and Autometers Systems Limited reserves the
right to make alterations and manufacture without notice. Products as delivered may
therefor differ from the descriptions and illustrations in this publication
Autometers Systems Ltd.
4B Albany Road, Chorlton-cum-Hardy
Manchester M21 0AW
Email: [email protected]
Phone: 00(44) 0161 861 9056
Fax: 0161 881 3745
www.autometers.co.uk
The meter is a 96 x 96 mm panel mounted meter with a depth of 70mm
The cut out hole for the panel meter is 92 x 92 mm.
Dimensions
Communications shield continuous
to the next meter
to the next meter
This meter is for
monitoring only
and can not be
connected to the
Autometers
Horizon Data
Monitoring System
Belden 9841 or Equal Cable Screened
Twisted pair with full Coax shielding
for RS 485 Modbus connection.
Red..…TX+
,
Black…TX-
,
Green…Shield
Connection
IMPORTANT NOTICE
The Q-180 series of meters are for monitoring
only and are not suitable for revenue collection.
The Q-180 series of meters has a different RS
485 Modbus Protocol and therefore cannot be
connected to the Horizon data monitoring
system
From the main Set-up menu, Use and to select the
CT option.
Set C.T.2 secondary current input.
Options: 5A or 1A
Default CT2: 5A
Long press to enter the CT2 routine.
Press for 2s, the CT2 setting will flash.
Use and to choose CT2 with 5A or 1A.
Press to return to the main menu.
C.T. (Current Transformer)
C.T. Rate (Current Transformer Primary)
Example of meter set at 200/5 amp
Example of how the display should look for a meter
programmed to 200/5 amp.
C.T.2 (Current Transformer Secondary)
To program the current ratio in the meter simply enter the
primary current.
eg. if you require the meter to be set at 200amp program
the numbers to be 0200.
Long press to enter the CT Rate routine.
Press for 2s, the CT rate setting will flash.
Use and to choose the first digit of the CT value.
Press to move the cursor to the right. When you have
entered the desired setting long press for
confirmation and then press to return to the main
menu.
Ref. Q180.
12
.20
20
60.8
25
18
12.7
98
62
96
3