2
Tech Support 770-844-4200
www.productivity2000.com
General Specifications
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
10000mW (Loop Power Included)
Enclosure Type
Open Equipment
Module Keying to Backplane Electronic
Module Location
Any I/O slot in a Productivity2000 System
Field Wiring
Use
ZIP
Link Wiring System ONLY. See “Wiring Options”
on page 5. Must use copper conductors 75°C or
equivalent.
EU Directive
See the “EU Directive” topic in the Productivity Suite
Help File. Information can also be obtained at:
www.productivity2000.com
Connector Type
24-Pin Molex Style 43025-2400
Weight
90g (3.2 oz)
Agency Approvals
UL 61010-1 and UL 61010-2-201 File E139594, Canada
and USA
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-
201 Safety)*
Output Specifications
Output Channels
16
Module Signal Output Range
4–20 mA sourcing
Signal Resolution
12-bit
Resolution Value of LSB
(least significant bit)
4-20 mA = 3.9 μA / count
1 LSB = 1 count
Data Range
0 to 4095 counts
Output Type (sourcing)
Current: 20mA max
Output Value in Fault Mode
Less than 4mA
Load Impedance
0–570 Ω (19.2 VDC), 0–690 Ω (21.6 VDC),
0–810 Ω (24VDC), 0–930 Ω (26.4 VDC),
0–1100 Ω (30VDC)
Minimum Load: 0Ω @ 0–45°C
125Ω @ 45–60°C ambient temperature
Maximum Inductive Load
1mH
Allowed Load Type
Grounded
Maximum Inaccuracy
1% of range (Including Temperature Drift)
Maximum Full Scale Calibration Error (Including
Offset)
±0.2% of range minimum
Maximum Offset Calibration Error
±0.2% of range maximum
Accuracy vs. Temperature
±75 PPM / °C maximum full-scale calibration change
(±0.005% of range / °C)
Max Crosstalk at DC, 50/60Hz
-72dB, 1 LSB
Linearity Error (End to End)
±4 LSB max., (±0.1% of full scale)
Monotonic with no missing codes
Output Stability and Repeatability
±2 count after 10 min. warm up (typical)
Output Ripple
±0.1% of full scale
Output Settling Time
0.3ms max., 5µs min. (full scale range)
All Channel Update Rate
1ms
Maximum Continuous Overload
Outputs open circuit protected
Field to Logic Side Isolation
1800VAC applied for 1 second (100% tested)
Type of Output Protection
Electronically current limited to 20mA or less
Output Signal at Power Up and Power Down
4mA
External DC Power Required
24VDC @ 410mA (includes loop power)
*Meets EMC and Safety requirements. See the D.O.C. for details.