background image

Power Supplies

P3-01AC  $147.00

There are two power supplies available; 
both provide isolated 24VDC, 5VDC, 
and 3.3 VDC to the Productivity3000 
bases.
The P3-01AC input power supply requires 
power from an external 100–240 VAC 
source.
The P3-01DC input power supply 
requires power from an external 24–48 
VDC source.

No Power Budgeting

No power budgeting is required with 
either power supply. Any combination of 
I/O modules may be installed in any slots 
without power budget considerations. 

P3-01AC

Terminal Block Specifications 

Number of Positions 

4 Screw Terminals

Pitch 

0.3 inch (7.62 mm)

Wire Range 

22–14 AWG (0.324 to 2.08 sq. mm) Solid Conductor 

22–14 AWG (0.324 to 2.08 sq. mm) Stranded Conductor 

3/64 inch (1.2 mm) insulation maximum

Screw Driver Width 

1/4 inch (6.5mm) maximum

Screw Size 

M3 size

Screw Torque 

7–9 inch-pounds (0.882 - 1.02 N·m)

P3-01AC User Specifications

Input Voltage Range (Tolerance)

100 to 240 VAC (-15% / +10%)

Rated Operating Frequency

50 to 60 Hz with ± 5% tolerance

Maximum Input Power

72W

Cold Start Inrush Current

12A 3mS

Maximum Inrush Current (Hot Start)

12A 3mS

Input Fuse Protection (Internal)

Micro fuse 250V, 2A, slow blow  

Non-replaceable

Efficiency

83%

Output

  24VDC @ 1.4 A   (±10%) 

   5VDC @ 2.1 A   (±5%) 

3.3 VDC @ 6.1 A  (±5%)

Maximum Output Power

57W Combined

Heat Dissipation

17W

Isolated User 24VDC Output

None

Output Protection for Over Current, 

Over Voltage, and Over Temperature

Self resetting for all three voltage outputs 

to base

Under Input Voltage Lock-out

55–65 VAC

Over Input Voltage Lock-out

265–280 VAC

Input Transient Protection

Varistor, plus input choke and filter

Operating Design Life

10 years at full load at 40°C ambient and 

5 years at 60°C ambient

P3-01AC General Specifications

Operating Temperature

0°C– 60°C (32°F–140°F),

Storage Temperature

-20ºC–70ºC (-4ºF–158ºF)

Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted 

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Enclosure Type

Open equipment

Voltage Withstand 

(dielectric)

1900 VDC applied for 2s

Insulation Resistance

>10M

V

 @ 500VDC

Module Location

Power supply slot in any local, expansion, or remote 

base in a Productivity3000

®

 System.

Weight

345g (12.1 oz)

Agency Approvals

UL508 file E157382, Canada & USA
UL1604 file E200031, Canada & USA
CE (EN61131-2*)
This equipment is suitable for use in Class 1, 

Division 2, Groups A, B, C and D or non-hazardous  

locations only. 

Hot-Swapping Information

Note: This device cannot be Hot Swapped.

IMPORTANT!

WARNING:

 

Explosion hazard – Substitution of components may 

impair suitability for Class I, Division 2.

*Meets EMC and Safety requirements. See the Declaration of Conformity for details.

AC Input Power Supply