background image

INSTALLATION INSTRUCTIONS

The device shall be mounted on DIN rail in a vertical and upright orientation.

For optimum operation and long life follow these instructions:

When the devices are installed side by side it is necessary to separate them by 

the following minimum distances:

• 

10 mm if UL certification is required.

• 

5 mm if UL certification is not required.

Make sure that sufficient air flow is provided for the device. Avoid placing 

raceways or other objects where they could obstruct the ventilation slits. 

Avoid mounting the devices above appliances generating heat; ideally locate 

them in the lower part of the panel.

Install the device in a place without vibrations.

Avoid routing conductors near power signal cables (motors, induction ovens, 

inverters, etc.). Use shielded cable for connecting signals; ground shield at one 

end only.

DEFAULT CONFIGURATION

• IP Address: 192.168.1.100

• Modbus Address: 1

• Default user name: admin

• Default password: password

WEEE compliance -

These devices comply with the WEEE directive. 

Dispose of properly.

AutomationDirect.com reserves the right to modify the characteristics of its products totally or in part without warning at any time. 

1st Edition, 01/2020

MECHANICAL DIMENSIONS

MM [IN]

MODBUS REGISTERS

Register

Description

Access

40002

Firmware [0]

RO

40003

Firmware [1]

RO 

40004

-Reserved-

RO

40005

-Reserved-

RO

40007

Node ID

R/W

40011

System Flags

R/W

40013

Watchdog timer

R/W

40031

Input Type, Channels 1–0

R/W

40032

Input Type, Channels 3–2

R/W

40033

Input Type, Channels 5–4

R/W

40034

Input Type, Channels 7–6

R/W

40041

Analog Input (0) - Ch0

RO

40042

Analog Input (1) - Ch1

RO

40043

Analog Input (2) - Ch2

RO

40044

Analog Input (3) - Ch3

RO

40045

Analog Input (4) - Ch4

RO

40046

Analog Input (5) - Ch5

RO

40047

Analog Input (6) - Ch6

RO

40048

Analog Input (7) - Ch7

RO

40050

Break Status

RO

41241

Offset Channel 0

R/W

41242

Offset Channel 1

R/W

41243

Offset Channel 2

R/W

41244

Offset Channel 3

R/W

41245

Offset Channel 4

R/W

41246

Offset Channel 5

R/W

41247

Offset Channel 6

R/W

41248

Offset Channel 7

R/W

FRONT PANEL LEDS

LED

COLOR

STATE

DESCRIPTION

PWR

GREEN

ON

Device powered

OFF

Device not powered

BLINK

Watchdog alarm

STS

YELLOW

OFF

Device in RUN mode

BLINK

Device in INIT mode

+

-

-VS

+VS

14–30 VDC

P

O

POWER SUPPLY (1)

-VS

INIT

P

Q

INIT FUNCTION (2)

NOTE: (1) To maintain the UL listing use a Class 2 or SELV and 

limited energy power supply.

See User Guide for instructions on using the INIT feature.

(2)

ON: Short INIT 

to -VS

CH 0–1

CH 2–3

CH 4–5

CH 6–7

ETH.

POWER

SUPPLY

ISOLATED ELECTRICAL SUBSYSTEMS 

Each block represents a subsystem which is isolated 

from each other subsystem.

INPUT 0

-

+

1

2

mV

Input V

COM0

Input

VOLTAGE

INPUT 1

-

+

3

4

mV

Input V

COM0

Input

INPUT 2

-

+

5

6

mV

Input V

COM1

Input

INPUT 3

-

+

7

8

mV

Input V

COM1

Input

ANALOG INPUTS

INPUT 4

-

+

9

10

mV

Input V

COM2

Input

INPUT 5

-

+

11

12

mV

Input V

COM2

Input

INPUT 6

-

+

13

14

mV

Input V

COM3

Input

INPUT 7

-

+

15

16

mV

Input V

COM3

Input

1

2

Input V

COM0

Input

INPUT 1

3

4

Input V

COM0

Input

INPUT 2

5

6

Input V

COM1

Input

INPUT 3

7

8

Input V

COM1

Input

+

Tc

-

+

Tc

-

+

Tc

-

+

Tc

-

INPUT 0

THERMOCOUPLE

INPUT 4

9

10

Input V

COM2

Input

INPUT 5

11

12

Input V

COM2

Input

INPUT 6

13

14

Input V

COM3

Input

INPUT 7

15

16

Input V

COM3

Input

+

Tc

-

+

Tc

-

+

Tc

-

+

Tc

-

NOTES:

“COM0”, “COM1”, “COM2” and “COM3” are each isolated commons.

Terminals “2” and “4” are internally connected to negative reference COM0.

Terminals “6” and “8” are internally connected to negative reference COM1.

Terminals “10” and “12” are internally connected to negative reference COM2.

Terminals “14” and “16” are internally connected to negative reference COM3.

  120.0

4.72

 

  50.7

2.00

 

  49.3

1.94

 

  100.0

3.94

 

3-WIRE

CONNECTOR

16-WIRE

CONNECTOR

  22.5

0.89

 

RESET BUTTON

STATUS

YELLOW LED

POWER

GREEN LED

PINOUT

Pin Description Channel

1

V0+

IN 0 / IN 1

2

COM0

3

V1+

4

COM0

5

V2+

IN 2 / IN 3

6

COM1

7

V3+

8

COM1

9

V4+

IN 4 / IN 5

10

COM2

11

V5+

12

COM2

13

V6+

IN 6 / IN 7

14

COM3

15

V7+

16

COM3

Reviews: