Automationdirect.com Productivity 3000 P3-08AD Quick Start Manual Download Page 6

Tech Support 770-844-4200

www.automationdirect.com/P3000

6

Linear Scaling

0

.5

1

1.55

2.25

3

4.55

6.75

7

0

0

0

0

0

0

0

0

1

2

3

4

5

6

6.5

7

0

0

0

0

0

0

0

Level Transmitter

Tank Level

7

0

0

0

0

0

0

0

Select the minimum and maximum 

values of the raw input signal. These 

values will relate to the minimum 

and maximum scaled values.

7
6
5
4
3
2
1
0

1   2   3   4   5   6   7  

Non-Linear Scaling

The Scale (Linear) function can be used to:
• Convert analog field input signals from the range which is native to the 

analog input module to an application specific range.

• Make other linear conversions in ranges appropriate to the application.

65535

220

12500

Tank Level

0

Control Valve 

Select the Input and Output tags appropriate 

for the application. Convert raw input signals 

to engineering units for use in the program, or 

convert engineering units to output signals for 

control purposes 

max 

 

 

 

 

 

 

 

min 

min 

 

max 

The Scale (Non-Linear) function can be used for Non-Linear  

applications.

Summary of Contents for Productivity 3000 P3-08AD

Page 1: ...ublications at any time without notice and without any obligation This publication may also discuss features that may not be available in certain revisions of the product P3 08AD Analog Input The P3 08AD Voltage Current Analog Input Module provides 8 channels for receiving 10 VDC 5 VDC 0 to 5 VDC 0 to 10 VDC and 0 to 20mA signals for use with the Productivity3000 Programmable Automation Controller...

Page 2: ...n current inputs only External DC Power Required 24VDC 20 25 33mA General Specifications Operating Temperature 0 to 60 C 32 to 140 F Storage Temperature 20 to 70 C 4 to 158 F Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 1800 VAC applied for 1 second Insulation Resistance 10MV ...

Page 3: ...iagram Voltage Input Circuits Current Sinking Input Circuits An Edison S500 32 R 0 032A fast acting fuse is recommended for all current loops COM V 4 Wire Voltage Transmitter 4 Wire Transmitter Optional Transmitter Power Supply AC or DC 24 VDC User Supplied Power 3 Wire Voltage Transmitter V COM 3 Wire Transmitter 032A 2 Wire 4 20 mA Transmitter fuse fuse 032A fuse 032A V I COM V I 3 Wire Current ...

Page 4: ...ted See hot swapping procedure for exceptions Align here Align here Step One Align circuit card with slot and press firmly to seat module into connector To install or remove terminal block cover press middle to flex cover AVERTISSEMENT Ne pas appliquer la puissance de champ avant l exécution des étapes qui suivent Consultez la procédure de remplacement à chaud pour les exceptions AVERTISSEMENT Ris...

Page 5: ... a User Tagname to each input point channel selected and to each Status Bit Item Module Configuration Wiring Options ZIPLink Connection System Cable ZIPLink Module Complete System ZIPLink pre wired terminal block cables 0 5m 1 6FT cable 1 0m 3 3FT cable 2 0m 6 6FT cable ZIPLink Modules Feed through ZL P3 CBL20 L ZL P3 CBL20 1L ZL P3 CBL20 2L ZL RTB20 Terminal Block with pigtail cable 0 5m 1 6FT ca...

Page 6: ...ng The Scale Linear function can be used to Convert analog field input signals from the range which is native to the analog input module to an application specific range Make other linear conversions in ranges appropriate to the application 65535 220 12500 Tank Level 0 Control Valve Select the Input and Output tags appropriate for the application Convert raw input signals to engineering units for ...

Page 7: ...er On Appears initially These screens will then auto cycle Fault Messages Appear in place of data during a fault condition Error Messages An existing error will be inserted into the cycling Status Info screen This screen will auto cycle with status information Input signal is OVER the maximum detectable by the module Input signal range minimum Voltage only Input signal 2mA Current only Note SPARE ...

Page 8: ...h Support 770 844 4200 www automationdirect com P3000 8 Document Name Edition Revision Date P3 08AD M 1st Ed Rev B 12 06 2017 Copyright 2017 AutomationDirect com Incorporated All Rights Reserved Worldwide ...

Reviews: