background image

1

Sales 800-633-0405

www.productivity2000.com

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement. (See www.productivity2000.com for details).

2000

WARNING:

 

To minimize the risk of potential safety problems, you should 

follow all applicable local and national codes that regulate the installation 

and operation of your equipment. These codes vary from area to area and 

it is your responsibility to determine which codes should be followed, and to 

verify that the equipment, installation, and operation are in compliance with 

the latest revision of these codes.

Equipment damage or serious injury to personnel can result from the 

failure to follow all applicable codes and standards. We do not guarantee 

the products described in this publication are suitable for your particular 

application, nor do we assume any responsibility for your product design, 

installation, or operation.

If you have any questions concerning the installation or operation of this 

equipment, or if you need additional information, please call Technical 

Support at 770-844-4200.

This publication is based on information that was available at the time it 

was printed. At AutomationDirect.com

®

 we constantly strive to improve 

our products and services, so we reserve the right to make changes to 

the products and/or publications at any time without notice and without 

any obligation. This publication may also discuss features that may not be 

available in certain revisions of the product.

Terminal Block Specifications

Number of positions

4 screw terminals

Wire Range

22-12 AWG (0.324 to 3.31 mm²) 

Solid / Stranded conductor 

3/64 in (1.2 mm) insulation maximum 

Use copper conductors, 75°C or equivalent

Screw Driver Width

1/4 in (6.5 mm) maximum

Screw Size

M3

Screw Torque

7-9 lb·in (0.882 - 1.02 N·m)

P2-01DCAC Power Supply

The P2-01DCAC Power Supply provides 

isolated power to the  

Productivity2000 base from an external 

12-24VDC or 24VAC source.

Warning  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Terminal Block Specifications  . . . . . . . . . . . . . . . . . 1

Power Supply Installation Procedure   . . . . . . . . . . . 2

Wiring   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

General Specifications   . . . . . . . . . . . . . . . . . . . . . . 3

User Specifications  . . . . . . . . . . . . . . . . . . . . . . . . . 3

Hot Swap Information  . . . . . . . . . . . . . . . . . . . . . . . 3

Reviews: