background image

1

Sales 800-633-0405

www.productivity1000.com

C1

2
3
4

C2

5
6
7
8

1

12-24VDC

INPUT

P1-08ND3

1000

P1-08ND3 Fast Response Input

The P1-08ND3 Fast Response Input Module 

provides eight inputs for switches and other 

devices connected to ground or supplies 

ranging from 12–24 VDC for use with the 

Productivity1000 system.

Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Module Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Schematic & Wiring Diagram  . . . . . . . . . . . . . . . . . . . .3

General Specifications  . . . . . . . . . . . . . . . . . . . . . . . . .4

Terminal Block Specifications . . . . . . . . . . . . . . . . . . . .4

Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

Terminal Block sold separately, (see wiring options on page 3).

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement (See www.productivity1000.com for details).

Input Specifications

Inputs per Module 

8 (sink/source)

Rated Voltage

12–24 VDC

Operating Voltage Range

10.2–26.4 VDC

Input Current

3.5 mA @ 12VDC

8.4 mA @ 24VDC

Maximum Input Current

10mA @ 26.4 VDC

Input Impedance

3k

Minimum ON Current

1.4mA

Maximum OFF Current

1mA

ON Voltage Level

>9.5 VDC

OFF Voltage Level

<4.5 VDC

OFF to ON, ON to OFF Response 

2ms Maximum, 1ms Typical

Status Indicators 

Logic Side (8 points)

Commons

2 (4 points/common)

Summary of Contents for Productivity 1000 P1-08ND3

Page 1: ... Terminal Block Specifications 4 Warning 4 Terminal Block sold separately see wiring options on page 3 Warranty Thirty day money back guarantee Two year limited replacement See www productivity1000 com for details Input Specifications Inputs per Module 8 sink source Rated Voltage 12 24 VDC Operating Voltage Range 10 2 26 4 VDC Input Current 3 5 mA 12VDC 8 4 mA 24VDC Maximum Input Current 10mA 26 4...

Page 2: ...08TD1 Wiring Diagram Module Installation WARNING Do not add or remove modules with field power applied Step One With latch in locked position align connectors on the side of each module and stack by pressing together Click indicates lock is engaged Step Three To unstack modules pull locking latch up into the unlocked position and then pull modules apart Step Two Attach field wiring using the remov...

Page 3: ...1 CBL10 1P ZL P1 CBL10 2P 3 Screw Terminal Block only P1 10RTB Quantity 1 4 Spring Clamp Terminal Block only P1 10RTB 1 Quantity 1 5 Accessories ZL RTB COM TW SD SL 1 TW SD MSL 1 ZL RTB20 ZL RTB20 1 2 1 Cable ZIPLink Module Complete System 2 ZL RTB COM provides a common connection point for power or ground P1 08ND3 Schematic and Wiring Diagram Single Supply 24VDC 24VDC C1 1 2 3 4 C2 5 6 7 8 1 2 3 ...

Page 4: ...ion or operation If you have any questions concerning the installation or operation of this equipment or if you need additional information please call Technical Support at 770 844 4200 This publication is based on information that was available at the time it was printed At AutomationDirect com we constantly strive to improve our products and services so we reserve the right to make changes to th...