Troubleshooting

4-20 mA Models

11..  SSeennssoorr  hhaass  nnoo  oouuttppuutt

A.. Power supply is not properly sized. 

Check power supply voltage and current rating.

B. Polarity is not properly matched. 

Check and correct wiring polarity

C. Split Core models: The core contact area may be dirty. 

Open the sensor and clean the contact area.

22..  O

Ouuttppuutt  ssiiggnnaall  ttoooo  llooww

A. The jumper may be set in a range too high for current

being monitored.

Move jumper to the correct range

.

B. The load current is not sinusoidal (ACT only). 

Select an ACTR transducer that works on distorted 
wave forms.

C. Monitored current is below minimum required.

Loop the monitored wire  through the  aperture
several times until the “sensed” current rises
above minimum

Sensed Amps = (Actual Amps) x (Number of Loops)

.

Count loops on the inside of the aperture.

33..  SSeennssoorr  iiss  aallwwaayyss  aatt  44m

mAA

A. Monitored load is not AC or is not on.

Check that the monitored load is AC and  is 
actually on.

44..  O

Ouuttppuutt  ssiiggnnaall  iiss  aallwwaayyss  aatt  2200m

mAA

A. The jumper may be set in a range  too low for  current

being monitored (750/2000 series have a 3-position
switch rather than a jumper).

Move jumper to the correct range

.

Troubleshooting 

0-10 VDC Models

11..  SSeennssoorr  hhaass  nnoo  oouuttppuutt

A. Polarity is not properly matched. 

Check and correct wiring polarity

B. Monitored load is not AC or is not on. 

Check that the monitored load is AC and is actually on.

C. Split Core models: The core contact area may be dirty. 

Open the sensor and clean the contact area.

22..  O

Ouuttppuutt  ssiiggnnaall  ttoooo  llooww

A. The jumper may be set in a range  too high for current

being monitored.

Move jumper to the correct range

.

B. Output load too low 

Check output load; be sure it is at least 100K

, and

preferably 1M

..

C. Monitored current is below minimum required.

Loop the monitored wire through the   aperture  sever-
al times until the “sensed” current rises above mini-
mum

Sensed Amps = (Actual Amps) x (Number of Loops)

.

Count loops on the inside of the aperture.

33..  O

Ouuttppuutt  ssiiggnnaall  iiss  aallwwaayyss  aatt  m

maaxxiim

muum

m

A. The jumper may be set in a range  too low for current

being monitored (750/2000 series have a 3-position
switch rather than a jumper). 

Move jumper to the correct range

.

Output Wiring

Connect control or monitoring wires to the sensor. Use

up to 12 AWG copper wire and tighten terminals to 5

inch-pounds torque.  Be sure the output load or loop

power requirements are met (see diagram at right).

Connection Notes:

• Captive screw terminals

• 12 - 22 AWG solid or stranded wire
• Observe polarity
• See label for ranges and jumper positions

Load 

(Controller,

Meter, etc.)

4-20mA

Transducer

24 VDC

Power

Supply

Load

(Controller,

Meter, etc.)

Voltage Output

Transducer

+

+

+

+

Description

ACT Series transducers combine a current transformer

and a signal conditioner into a single package. This

provides  higher  accuracy,  lower  wiring  costs,  easier

installation and saves valuable panel space.
ACT  Series  are  available  in  fixed  or  split  core  with 

4-20 mA or 0-10 VDC outputs. Select ACT Series for

constant  speed  loads,  On/Off  loads  or  sinusoidal

waveform loads. 
ACTR Series units are available in 4-20 mA output only.

The ACTR Series provides a “True RMS” output. Select

ACTR Series for variable speed, SCR controlled loads or

non-sinusoidal waveform loads.

Installation

For All Versions

Run wire to be monitored through the opening in the

sensor. ACT and ACTR Series transducers work in the

same environment as motors, contactors, heaters, pull-

boxes  and  other  electrical  enclosures.  They  can  be

mounted  in  any  position.  Leave  at  least  one  inch

distance  between  the  sensor  and  other  magnetic

devices.

Split-Core Versions (-S Suffix)

Press  the  tab  in  the  direction  as  shown  to  open  the

sensor. After placing the wire in the opening, press the

hinged portion firmly downward until a definite click is

heard and the tab pops out fully.

KEEP SPLIT-CORE SENSORS CLEAN.

Silicone grease is factory applied on the mating surfaces

to  prevent rust and improve performance. Be careful

not to allow grit or dirt onto the grease in the contact

area. Operation can be impaired if the mating surfaces

do  not  have  good  contact.  Check  visually  before

closing.

N

A

E

L

C

 

S

R

O

S

N

E

S

 

E

R

O

C

-

T

I

L

P

S

 

P

E

E

K

.

!t

n

a

t

r

o

p

m

I

 t

c

a

t

n

o

C

 

p

e

e

K

!

N

A

E

L

C

 

a

e

r

A

 

n

e

p

O

 

o

T

 

b

a

T

 

s

s

e

r

P

.

e

g

n

i

H

 

d

r

a

w

o

T

Range Selection

ACT Series transducers feature field selectable ranges.

The  ranges  are  factory  calibrated,  eliminating  time

consuming and inaccurate field setting of zero or span.

1. Determine the normal operating amperage of the 

monitored circuit

2. Select the range that is equal to or slightly higher than 

the normal operating amperage.

3. Place the range jumper in the appropriate position

(750/2000 series have a 3-position switch rather than a
jumper).