T1K–MODBUS
Specifications
Installation and
Safety Guidelines
2–8
T1K–MODBUS Specifications
MODBUS Port Pin–out and Wiring
MODBUS Port Pin Descriptions
1
5V
5 VDC
2
TXD2
Transmit Data (RS232C)
3
RXD2
Receive Data (RS232C)
4
RTS2
Ready to Send (RS–232C)
5
CTS2
Clear to Send (RS–232C)
6
RXD2–
Receive Data – (RS–422)
7
0V
Logic Ground
8
0V
Logic Ground
9
TXD2+
Transmit Data + (RS–422)
10
TXD2 – Transmit Data – (RS–422)
11
RTS2 + Request to Send + (RS–422)
12
RTS2 – Request to Send – (RS–422)
13 RXD2 + Receive Data + (RS–422)
14 CTS2 + Clear to Send + (RS422)
15
CTS2 – Clear to Send – (RS–422)
15-pin Female
D Connector
1
5
11
15
10
6
RS–232C
Point-to-point
DTE Device
2
TXD
3
RXD
4
RTS
5
CTS
7
0V
Signal GND
RXD
TXD
PC/PLC
MODBUS
Master
MODBUS
Port
RXD+
RXD–
TXD+
TXD–
Signal GND
RS–422
Network
MODBUS
Port
9
TXD+
10 TXD–
13 RXD+
6
RXD–
11 RTS+
12 RTS–
14 CTS+
15 CTS–
7
0V
PC/PLC
MODBUS
Master
Termination
Resistor on
last slave only
The recommended cable
for RS422 is Belden
9729 or equivalent.
RS–485
Network
9
TXD+
13 RXD+
6
RXD–
10 TXD–
11 RTS+
Signal GND
TXD+ / RXD+
PC/PLC
MODBUS
Master
MODBUS
Port
14 CTS+
12 RTS–
15 CTS_
7
0V
TXD– / RXD–
Termination
Resistor on
last slave only