Automation Direct Stratus TA20 Series User Manual Download Page 11

11

w w w . a u t o m a t i o n d i r e c t . c o m

STRATUS TA20 Series Industrial Air Conditioners User Manual
1st edition RevA.

System Operation

Once the STRATUS system has been installed onto the  
enclosure and the power has been connected to a properly 
grounded power source with adequate voltage and current 
supply, the unit is ready for operation. As soon as electrical 
power is supplied to the STRATUS system and the power 
switch located on the back of the unit is turned on, the  
evaporator fan will start to operate. The fan will run 

 

continuously so that the controller can monitor the enclosure’s 
internal temperature. The enclosure temperature will be 
displayed on the face of the controller. If the enclosure  
temperature is greater than the cooling setpoint of 95°F plus 
factory-set temperature differential of 5°F, the snowflake status 
LED will be ON and the compressor will turn on. After the 
refrigerant pressure builds up to a factory setpoint of 300 psi, 
the condenser fan will operate.
This signifies that the cooling system has begun operation to 
remove heat and humidity  from the enclosure. If the heat 
load within the enclosure is less than the cooling capacity of 
the STRATUS system, the temperature on the digital display 
will begin to drop. When the temperature inside the enclosure 
drops to the factory-set 95°F setpoint, the compressor will 
cycle off. The cool air evaporator fan will continue to operate,  
circulating air within the enclosure. The compressor fan will 
cycle off if the pressure drops below the factory setpoint. 

Example:  “Cooling on” @ 100°F; “Cooling off” @ 95°F. 

Set point is 95°F plus 5°F Hysteresis= Cooling on @ 100°F.

If the compressor attempts to cycle within 5 minutes, the 
snowflake status LED will FLASH. This indicates that the 
compressor’s automatic  timer is working (the anti-short-cycle 
timer is factory set at 5 minutes). At the end of 5 minutes, the 
compressor will begin to operate and the snowflake status LED 
will remain ON while the compressor remains on.

System Faults

If any of the critical control parameters exceed limits, the 
compressor is turned off, an alarm condition is indicated on the 
front panel, and an alarm contact operates for remote alarming.
Three main conditions can shut down the AC compressor: 

• The condenser high temperature alarm  

• The evaporator coil alarm  

• The compressor thermal overload 

In the event that the condenser coil overheats, a condenser high 
temperature alarm, 

HA2

, will flash on the display of the digital 

temperature controller, the remote alarm contact will operate, 
and the compressor will turn off after a 3-minute time delay.
In the case that the evaporator coils ice up or there is a leak, 
an evaporator coil alarm, 

CA

, will flash on the display of the 

Digital Temperature Controller, the remote alarm contact will 
operate, and the compressor will turn off after a 2-minute time 
delay.
A thermal overload protects the compressor against faults. In 
the event that the snowflake status LED is not flashing on the 
display and the compressor is not running, an internal fault 
may have occurred on the unit. Refer to the Troubleshooting 
Guide in this manual.

Alarm Conditions

If any of the alarm parameters exceed limits, an alarm condition 
is indicated on the front panel and an alarm contact operates 
for remote alarming.
The temperature alarms are delayed for 30 minutes at initial 
startup. If the preset high temperature limit is exceeded for 
more than 3 minutes, the compressor continues to operate but 
there is a maximum temperature alarm, 

HA

, flashing on the 

display. 
If the preset low temperature limit of 45°F is exceeded for 
more than 3 minutes, there is a minimum temperature alarm, 

LA

, flashing on the display. (The compressor turns off at the 

temperature setpoint.)
In case of a fault in the enclosure temperature probe “P1”, 
the start and stop of the compressor are delayed for 5 and 15 
minutes, respectively. A 

P1

 alarm will display and the remote 

alarm contact will operate immediately.
In case of a fault in the condenser temperature probe “P2”, a 

P2

 alarm will flash on the display and the remote alarm contact 

will operate immediately.
If the evaporator coil pressure drops below 10 psi for more 
than 2 minutes, there is an evaporator coil alarm, 

CA,

 and the 

compressor turns off. After the pressure is increased to 25 psi, 
the 

CA

 alarm is cleared and the compressor operates after a 

5-minute time delay.

Time

Temperature

Compressor

SET

ON

 

Summary of Contents for Stratus TA20 Series

Page 1: ...1 w w w a u t o m a t i o n d i r e c t c o m STRATUS TA20 Series Industrial Air Conditioners User Manual 1st edition RevA TA20 Series User Manual...

Page 2: ...clude the Manual Number and the Manual Issue both shown below when communicating with Technical Support regarding this publication Manual Number Stratus_TA20_UM_WMO_1ed Issue 1st Edition Issue Date 12...

Page 3: ...ox 6 Nameplate Information 6 Inspecting the Equipment 6 Basic Operation 7 Features 8 Unit Specifications 8 Preliminary Testing 10 Mounting the Air Conditioner 10 System Operation 11 System Faults 11 A...

Page 4: ...en toute s curit Toute personne qui installe ou utilise cet quipement doit lire la pr sente publica tion et toutes les autres publications pertinentes avant de l installer ou de l utiliser Afin de r...

Page 5: ...vailable weekdays from 9 00 a m to 6 00 p m Eastern Time We also encourage you to visit our web site where you can find technical and non technical information about our products and our company Visit...

Page 6: ...he pallet not top side up other freight on top damaged or wet should be refused delivery Contact the shipper immediately upon discovery of shipping damage to schedule inspection by the freight company...

Page 7: ...of 95 F plus the temperature differential of 5 F As the refrigerant pressure builds to a factory setpoint the condenser fan turns on to force air flow across the coils Refrigerant low pressure and hig...

Page 8: ...ser inlet air filter Thermal expansion valve provides high performance over wide temperature range Internally insulated to minimize case heat loss Schrader valves on low AND high pressure service port...

Page 9: ...26 4X 230 60 2 00 45 12 00 NEMA Type 4 Unit Specifications Model BTU H Max Ambient Temperature Standard Max Ambient Temperature Volts Hertz Running Amps Unit Weight lb Refrigerant Type Refrigerant Amt...

Page 10: ...with the unit Using the template supplied determine where the air conditioner is to be mounted and make sure that all required cuts and holes will not interfere with or damage the enclosure There mus...

Page 11: ...condition is indicated on the front panel and an alarm contact operates for remote alarming Three main conditions can shut down the AC compressor The condenser high temperature alarm The evaporator co...

Page 12: ...t unit F Flashing Programming phase Digital Temperature Controller Overview The microprocessor based digital temperature controller performs the functions of controlling the enclosure temperature whil...

Page 13: ...ey to display its value 3 Press the UP or DOWN arrow key to change its value 4 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds w...

Page 14: ...fter initial 30 min delay Alarm relay operates HA2 Condenser high temperature P2 L 145 F for 3 minutes Alarm relay operates compressor off LA2 Condenser low temperature P2 l 50 F for 3 minutes Alarm r...

Page 15: ...oil cleaning compounds and thorough back flush rinsing Refer to directions on the cleaning compounds selected Acid wash is not recommended as it reduces the life of the coil Note Do not use solvents t...

Page 16: ...locked Installation must meet minimum clearance for condenser air flow Adjacent unit heating air Install baffle deflector or move unit s Perform touch test Compressor hot 190 F Suction accumulator col...

Page 17: ...a u t o m a t i o n d i r e c t c o m STRATUS TA20 Series Industrial Air Conditioners User Manual 1st edition RevA Typical Frame Size TA20 0 1000 BTU H Units Dimensions All dimensions inches millimete...

Page 18: ...5 18 STRATUS TA20 Series Industrial Air Conditioners User Manual 1st Edition RevA w w w a u t o m a t i o n d i r e c t c o m Typical Frame Size TA20 1 2000 BTU H Units Dimensions All dimensions inche...

Page 19: ...RATUS TA20 Series Industrial Air Conditioners User Manual 1st edition RevA 1 8 0 0 6 3 3 0 4 0 5 Cutout for Typical Frame Size TA20 0 1000 BTU H Units Dimensions All dimensions inches millimeters Cuto...

Page 20: ...1 8 0 0 6 3 3 0 4 0 5 20 STRATUS TA20 Series Industrial Air Conditioners User Manual 1st Edition RevA Schematic 1000 BTU 48VDC...

Page 21: ...21 w w w a u t o m a t i o n d i r e c t c o m STRATUS TA20 Series Industrial Air Conditioners User Manual 1st edition RevA Schematic 1000 BTU 120V...

Page 22: ...1 8 0 0 6 3 3 0 4 0 5 22 STRATUS TA20 Series Industrial Air Conditioners User Manual 1st Edition RevA Schematic 2000 BTU 120 240VAC...

Page 23: ...cement Parts Wiring Terminal Blocks for Stratus Air Conditioners Manufacturer Manufacturer Part Description 2000 BTU Models Phoenix Contact 1718504 Plug Component Phoenix Contact 1716522 Feedthrough H...

Page 24: ...1 8 0 0 6 3 3 0 4 0 5 24 STRATUS TA20 Series Industrial Air Conditioners User Manual 1st Edition RevA...

Reviews: