![Automation Direct Rhino PSB12-015-P Installation Instructions Download Page 2](http://html1.mh-extra.com/html/automation-direct/rhino-psb12-015-p/rhino-psb12-015-p_installation-instructions_3021788002.webp)
Input (AC)
Nominal input voltage
100-240VAC
Voltage range
85-264VAC (DC input range 120-375 VDC)
Frequency
47-63Hz (0 Hz @ DC input)
Nominal current
0.37A @ 115VAC, 0.22A @ 230VAC
Inrush current limitation. I2t (+25 °C) typ.
< 30A @ 115VAC, < 65A @ 230VAC
Mains buffering at nominal load (typ.)
> 22ms @ 115VAC, > 110ms @ 230VAC
Turn-on time
< 2.5 sec.
Internal fuse
T 3.15 AH / 250 V (non-replaceable)
Leakage current
< 1 mA
Output (DC)
Nominal output voltage / Adjustment range
12VDC ± 2 % / 11-14VDC (maximum power < 15W)
Output Power
15W
Nominal current
1.25A
Derating above +50 °C [122°F]
2.5 % / °C. (>70°C [158°F] 4 % / °C.)
Startup with capacitive loads
Max. 5,000 µF
Max. power dissipation idling / nominal load approx.
m
3.2W
Efficiency (at 400 VAC and nominal values)
83.5% min.@ 115VAC & 83% min. @ 230 VAC
Residual ripple/ peak switching (20 MHz) (at nominal values)
< 100mV
Parallel operation
With decoupling diode
General Data
Type of housing
Plastic (PC), closed
Signals
Green LED DC OK
MTBF
> 300,000 hrs.
Dimensions (L x W x H)
100 mm x 32 mm x 100 mm [3.94 in x 1.26 in x 3.94 in]
Weight
0.175 kg [0.39 lb]
Connection method
Screw connection
Wire size / torque
0.32-2.1 mm² (AWG 22-14) / 0.79Nm (7.0lb in)
Stripping length
7 mm [0.28 in] or use suitable lug to crimp
Ambient Operating temperature
-20°C to +50°C [-4°F to 122°F]
Storage temperature
-25°C to +85°C [-13°F to 185°F]
Humidity at +25°C, no condensation
<95 % RH
Shock
30g half sine, 3 times per direction, 6 directions, per IEC60068-2-27
Vibration (Non-operating)
10 to 150Hz, 5 g, 90 min. each axis per IEC60068-2-6
Pollution degree
2
Climatic class
3K3 according to EN 60721
Certification and Standards
Electrical equipment of machines
IEC60204-1 (over voltage category III)
Electronic equipment for use in electrical power installations
EN62477-1 / IEC62103
Safety entry low voltage
PELV (EN 60204), SELV (EN 60950)
Electrical safety (of information technology equipment)
UL/C-UL recognized to UL60950-1, CSA C22.2 No.60950-1,
CB scheme to IEC60950-1
Industrial control equipment
UL listed to UL508, CSA to CSA C22.2 No.107.1-01
Protection against electric shock
DIN 57100-410
CE
In conformance with EMC directive 2014/30/EU and low voltage directive 2014/35/EU
EMC for ITE
EN55032, EN61000-3-2, EN61000-3-3, EN55024
EMC for industrial
EN55011, EN61000-6-2
Limitation of mains harmonic currents
N/A
RoHS
Yes
3PET
E198298
249074
Safety and Protection
Transient surge voltage protection
VARISTOR
Current limitation at short-circuits approx.
Isurge = 150 % of Po
max
typically
Surge voltage protection against internal surge voltages
Yes
Isolation voltage:
Input/output (type test/routine test)
Input/GND (type test/routine test)
Output/GND (type test/routine test)
4 kVAC / 3 kVAC
1.5 kVAC / 1.5 kVAC
1.5 kVAC / 500 VAC
Protection degree
IPX0
Safety class
Class I with GND connection
Technical Data For PSB12-015-P