12.3.3 Resolution
Signal resolution > 13 bit
12.3.4 Influence of ambient temperature
< 0.02 %/K (0.01 %/°F) of measuring range
12.3.5 Warm-up period
10 minutes
12.4 Installation
12.4.1 Mounting location
Panel housing (LPM1-A-PNL)
The device is designed for use in a panel.
Required panel cutout 45x92 mm (1.77x3.62 in)
Field housing (LPM1-A-ENC, LPM1-A-HAZ)
The field housing version is designed for use in the field. The unit is
mounted directly on a wall, or on a pipe with a diameter of up to 2 inches
with the aid of an optional mounting bracket
(LPM1-BKT1)
.
12.4.2 Orientation
Panel housing
The orientation is horizontal.
Field housing
The device must be mounted in such a way that the cable entries point
downwards.
12.5 Environment
12.5.1 Ambient temperature range
–40 to 60 °C (–40 to 140 °F)
At temperatures below –25 °C (–13 °F) the readability of the display
can no longer be guaranteed.