Parameter page in SuperVision. Refer to one 
of the UNI technical instructions documents 
for details.

If you use a flow sensor with the U551, use 
the Airflow microblock in the U551’s GFB.

To connect the sensor, make sure the U551’s 
power is off first. Attach the total or high 
pressure line from the VAV box to the 
module’s HI side, and attach the static 
pressure line to the module’s LO side. 
Connect the USF to the U551 as shown in 
Figure 11

To ensure an accurate reading from the flow 
sensor, use the Airflow microblock in the 
module’s GFB. You must calibrate this 
microblock using the instructions on the FB’s 
Properties page in WebCTRL or Parameter 
page in SuperVision. Refer to the 

Eikon for 

WebCTRL Microblock Reference Guide

 or the 

Eikon Microblock Reference Guide 

for more 

information.

 

NOTE

When installing the UDF, be sure to 

permanently remove the W4 jumper as 
shown in Figure 12 prior to performing test 
and balance. 

Writing GFBs for the U551

Depending on whether you are using a 
WebCTRL or a SuperVision system, you must 
use either Eikon for WebCTRL or Eikon 3.0a 
or later to create GFBs for the U551. Be sure 

 Figure 11. Using the UDF

4"

10.2 cm

2.5"

6.4 cm

High

High

4321

STATIC

PRESSURE

TOTAL

PRESSURE

Flow #1

Flow #2

Low

Low

6"

15.2 cm

U module

Maximum Cable Length 4 ft.
Use 20 Gauge Wire

or ALC cable (part no. 235012)

NOTE: When making a sensor cable, disregard the

numbers imprinted on the plastic connector.

 Figure 12. Removing the W4 Jumper

Gnd

IN-3

Gnd

IN-2

Gnd

IN-1

Remove
W4 jumper

W4

W3

W2

BOOT

Summary of Contents for U551

Page 1: ...ed trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions U55 1 Using the U551 2 Specifications 2 Job Start Up 3 Job Start Up for WebCTRL 3 Job Start Up for SuperVision 3 Start Up Checklist 4 Mounting 4 Addressing 4 Power Wiring 4 Communications Wiring 5 Communicating Through the LogiStat Port 6 Input Wiring 7 Using the LogiStat 7...

Page 2: ...kon User s Guide for more information NOTE To operate this module based on a schedule the UNI must be networked with a gateway module U551 modules have been designed to meet low end high volume terminal control applications As a result time critical applications such as short time delays and trend intervals of less than one minute should not be used with these modules ALC recommends that all time ...

Page 3: ...need these items to properly start up and support U cards UNI 16 with the U1M module driver UNI 30 with the U3M module driver UNI 32 with the UNM module driver or UNI 59 with the U5M module driver Eikon 3 0a or later Figure 1 U551 Layout and Dimensions Ones Tens Gnd Temp Sw LS5v L o g i S t a t Tx Enclosed Energy 88FO E143900 TYPE 000553 Management Equipment R Run n c Gnd AO 1 DO 5 DO 4 DO 3 DO 2 ...

Page 4: ...fied This number is shown on the UNI Properties page in WebCTRL or on the UNI Status page in SuperVision Power Wiring The Unet follows the same specifications as a legacy CMnet Refer to the Technical Handbook for details on legacy CMnets Also refer to the Technical Handbook for detailed information on daisy chain star and hybrid wiring configurations There is a special wire available that contains...

Page 5: ...is unshielded Shielded cable is not required for the Unet In most circumstances you should have a PROT485 within 250 feet of any U line module on the Unet for surge protection However depending on the frequency of electrical surges in your area the 250 foot recommendation may vary For example if you have frequent electrical storms in your area you may want to use more PROT485s if you have few elec...

Page 6: ...hat it can provide power to the APT If the LED is not on you can provide power to the APT using the Supplemental Power 5V dc connection see Figure 6 on page 7 and the special power cable to a laptop keyboard jack or an external supply such as a 5V dc transformer 3 Define the connection type In SuperVision v3 0 define the connection as Access Port In SuperVision v2 6 define the connection as Direct...

Page 7: ...behind the input port You must remove the cover to access the pull up jumpers The output impedance of a 0 to 5VDC source must not exceed 10kohms The input impedance of the U551 is approximately 1Mohm Dry Contact A 5VDC wetting voltage is used to detect contact position This results in a 0 5mA maximum sense current when the contacts are closed No pulse accumulation inputs are allowed in U551 FBs ex...

Page 8: ...le Be sure the U551 s power is off before wiring any inputs or outputs Connect the output wiring to the screw terminals on the module To verify each output s operation lock the output to a known condition on the Function Block s Properties page in WebCTRL or the Parameter page in SuperVision then make sure the equipment operates as specified Using Flow Sensors The U551 controls air flow in the zon...

Page 9: ...ge in WebCTRL or Parameter page in SuperVision Refer to the Eikon for WebCTRL Microblock Reference Guide or the Eikon Microblock Reference Guide for more information NOTE When installing the UDF be sure to permanently remove the W4 jumper as shown in Figure 12 prior to performing test and balance Writing GFBs for the U55 1 Depending on whether you are using a WebCTRL or a SuperVision system you mu...

Page 10: ...ence Guide You do not need to use BACnet microblocks when writing the GFB unless you have a BACview Keypad Display connected to the UNI You must then use BACnet point microblocks to access U551 points through the keypad Point Identifiers A point can be identified in WebCTRL by its point number and point type in SuperVision a point is identified by its channel number On both systems expander number...

Page 11: ...gital 21 IN 2 Thermistor 32 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 Volts 32 0 to 5V Digital 22 Sw Thermistor A3 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 Digital B3 LogiStat Temp Thermistor A1 or A2 45 to 100 F 7 22 to 37 8 C 0 00 0 00 15 88 15 69 LogiStat Thermistor 33 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 IN 3 or UDF 2 Volts 33 0 to 5V Digital 23 UDF 2 Flow CFM Flow inpu...

Reviews: