Automated Logic MX16160 Technical Instructions Download Page 4

Revised 9/13/00 • MX16160

4

© 2000 Automated Logic Corporation

6. Set the module’s address. Refer to 

“Addressing” on page 3 for details about 
setting the address.

7. Turn the module’s power switch on.

When the module turns on, the Run and 
Power LEDs turn on. The Run LED begins 
blinking and the Error LED turns off. See 
“LEDs” on page 7 to troubleshoot the 
LEDs. If the module does not respond, call 
Technical Support at (770) 429-3002.

 

Inputs

The MX16160 module has sixteen universal 
inputs to accept the types of signals listed 
below. Refer to Table 1 for information about 
wire length, gauge, and shielding.

• Thermistor: Precon type 2 (10kohm at 

77°F). Input voltages should range 
between 0.489V and 3.825V for 
thermistors.

• 0 to 5VDC: The output impedance of a 0 

to 5VDC source must not exceed 
10kohms. The input impedance of the 
MX16160 is approximately 1Mohm.

• 0 to 20mA: The input resistance on the 

“A” input is 250 Ohms. The “B” terminal 
supplies a voltage source to power the 
4-20mA transducer. The “B” terminal is 
capable of supplying 18 to 24VDC, but 
the total current of all “B” terminals 
must not exceed 320mA. If the voltage 
measured from the “B” terminal to Gnd 
is less than 18VDC, you need to use an 
additional external power supply. 

• Dry Contact: A 5VDC wetting voltage is 

used to detect contact position. This 
results in a 0.5mA maximum sense 
current when the contacts are closed. 

The MX16160 accumulates up to 15 input 
pulses per second.

1. Be sure the MX16160’s power is off before 

wiring any inputs or outputs. 

2. Connect the input wiring to the screw 

terminals on the module as shown in 
Figure 3 on page 5.  

NOTE

If a 4-20 mA sensor uses an 

external 24VAC power supply, connect 
one leg of the 24VAC supply to the module 
ground.  

3. Set the configuration jumper for each 

input to indicate the type of input used. 
Make sure the jumper is positioned 
correctly, and be sure to grip the jumper 
by the sides only. See Figure 4 on page 5.

4. For each input, enter the channel number, 

offset, and gain on the Function Block’s 
Parameter page in SuperVision. Valid 
channel numbers are listed in “Channel 
Numbers” on page 6
.

5. To verify each input’s operation, have 

each sensor create a known value and  
compare it to the condition reported on 
the FB’s Status page.   

 

 

 

Table 1. Input wiring restrictions

Input

Maximum 
Length

Minimum 
Gauge

Shielding

0 to 5VDC

50 feet
15 meters

24AWG

shielded and 
grounded to 
module’s 

B

 

or Gnd 
terminal

Thermistor
Dry contact

50 feet
15 meters

24AWG

shielded and 
grounded to 
module’s 

B

 

or Gnd 
terminal

0 to 20mA

150 feet
46 meters

20AWG

unshielded

Summary of Contents for MX16160

Page 1: ...perVision Eikon Alert and InterOp are registered trademarks of Automated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions MX1 6 1 60 Using the MX16160 2 Specifications 3 Mounting 3 Addressing 3 Power Wiring 3 Inputs 4 Digital Outputs 5 Channel Numbers 6 Troubleshooting 7 LEDs 7 Protec...

Page 2: ...nce in which case the user will be required to correct the interference at his own expense Figure 1 Module Dimensions and Layout 11 5 16 28 73cm 11 5 16 28 73cm 3 4 1 9cm 5 5 8 14 29cm I O Expansion Address Switch Power and Run LEDs Gnd and 24VAC Terminals M ode Se lect U niversal Inpu t 1 16 0 5Vdc d ry contact T herm istor 0 20 mA I O Exp ander A dd ress 1 s R A B 3 2 1 A IN 9 B B A 4 6 5 A B 7 ...

Page 3: ...0 s power is off The MX16160 only reads the address when the module is turned on The MX16160 uses a rotary switch to assign the module s expander number If the module s expander address is three set the switch to three as shown in Figure 2 Power Wiring Whenever possible make sure the module s power and communications connections are working properly before connecting any input or output points CAU...

Page 4: ...ed to use an additional external power supply Dry Contact A 5VDC wetting voltage is used to detect contact position This results in a 0 5mA maximum sense current when the contacts are closed The MX16160 accumulates up to 15 input pulses per second 1 Be sure the MX16160 s power is off before wiring any inputs or outputs 2 Connect the input wiring to the screw terminals on the module as shown in Fig...

Page 5: ...uto mode by setting the HOA switches see Figure 1 on page 2 for the switches location Table 2 shows the status of the digital output based on the output s configuration and the HOA switch position Figure 3 Input Wiring Figure 4 Jumper Position PWR PWR PWR OUT OUT GND GND GND 0 5VDC DRY CONTACT PASSIVE TRANSDUCER 4 20mA 12V or 24V LOOP INPUT THERMISTOR 3 WIRE 4 20mA ISOLATED AC or DC POWER SUPPLY 4...

Page 6: ... 6 Digital HOA Status 16 86 DO 7 Digital HOA Status 17 87 DO 8 Digital HOA Status 18 88 DO 9 Digital HOA Status 19 89 DO 10 Digital HOA Status 1A 8A DO 11 Digital HOA Status 1B 8B DO 12 Digital HOA Status 1C 8C DO 13 Digital HOA Status 1D 8D DO 14 Digital HOA Status 1E 8E DO 15 Digital HOA Status 1F 8F DO 16 Digital HOA Status 10 80 Use digital input microblocks to monitor the status of HOA Switch...

Page 7: ...100 6 C 0 00 0 00 15 88 15 69 mA or Volts 38 0 to 20mA 0 to 5V Digital 28 UI 9 Thermistor 39 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 39 0 to 20mA 0 to 5V Digital 29 UI 10 Thermistor 3A 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 3A 0 to 20mA 0 to 5V Digital 2A UI 11 Thermistor 3B 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 3B 0 to 20mA 0 to 5V Di...

Reviews: