Technical Instructions

MX16160

Using the MX16160 2
Specifications 3
Mounting 3
Addressing 3
Power Wiring 3
 Inputs 4
Digital Outputs 5
Channel Numbers 6
Troubleshooting 7

LEDs 7
Protection 7
Production Date 7

Summary of Contents for MX16160

Page 1: ...perVision Eikon Alert and InterOp are registered trademarks of Automated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions MX1 6 1 60 Using the MX16160 2 Specifications 3 Mounting 3 Addressing 3 Power Wiring 3 Inputs 4 Digital Outputs 5 Channel Numbers 6 Troubleshooting 7 LEDs 7 Protec...

Page 2: ...nce in which case the user will be required to correct the interference at his own expense Figure 1 Module Dimensions and Layout 11 5 16 28 73cm 11 5 16 28 73cm 3 4 1 9cm 5 5 8 14 29cm I O Expansion Address Switch Power and Run LEDs Gnd and 24VAC Terminals M ode Se lect U niversal Inpu t 1 16 0 5Vdc d ry contact T herm istor 0 20 mA I O Exp ander A dd ress 1 s R A B 3 2 1 A IN 9 B B A 4 6 5 A B 7 ...

Page 3: ...0 s power is off The MX16160 only reads the address when the module is turned on The MX16160 uses a rotary switch to assign the module s expander number If the module s expander address is three set the switch to three as shown in Figure 2 Power Wiring Whenever possible make sure the module s power and communications connections are working properly before connecting any input or output points CAU...

Page 4: ...ed to use an additional external power supply Dry Contact A 5VDC wetting voltage is used to detect contact position This results in a 0 5mA maximum sense current when the contacts are closed The MX16160 accumulates up to 15 input pulses per second 1 Be sure the MX16160 s power is off before wiring any inputs or outputs 2 Connect the input wiring to the screw terminals on the module as shown in Fig...

Page 5: ...uto mode by setting the HOA switches see Figure 1 on page 2 for the switches location Table 2 shows the status of the digital output based on the output s configuration and the HOA switch position Figure 3 Input Wiring Figure 4 Jumper Position PWR PWR PWR OUT OUT GND GND GND 0 5VDC DRY CONTACT PASSIVE TRANSDUCER 4 20mA 12V or 24V LOOP INPUT THERMISTOR 3 WIRE 4 20mA ISOLATED AC or DC POWER SUPPLY 4...

Page 6: ... 6 Digital HOA Status 16 86 DO 7 Digital HOA Status 17 87 DO 8 Digital HOA Status 18 88 DO 9 Digital HOA Status 19 89 DO 10 Digital HOA Status 1A 8A DO 11 Digital HOA Status 1B 8B DO 12 Digital HOA Status 1C 8C DO 13 Digital HOA Status 1D 8D DO 14 Digital HOA Status 1E 8E DO 15 Digital HOA Status 1F 8F DO 16 Digital HOA Status 10 80 Use digital input microblocks to monitor the status of HOA Switch...

Page 7: ...100 6 C 0 00 0 00 15 88 15 69 mA or Volts 38 0 to 20mA 0 to 5V Digital 28 UI 9 Thermistor 39 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 39 0 to 20mA 0 to 5V Digital 29 UI 10 Thermistor 3A 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 3A 0 to 20mA 0 to 5V Digital 2A UI 11 Thermistor 3B 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 3B 0 to 20mA 0 to 5V Di...