Automated Logic M220NX Technical Instructions Download Page 3

Revised 4/3/00 • M220nx

3

© 2000 Automated Logic Corporation

cause harmful interference in which case the
user will be required to correct the
interference at his own expense.

Specifications

Power

24VAC ± 10%, 50-60Hz (24VAC

±10%, 60Hz for UUKL Smoke Control
Systems), 20VA power consumption
(single Class 2 source only, 100VA or
less).

Inputs

two universal inputs, configurable

for 0-5VDC, 0-20mA, or thermistor.

Input Resolution

10 bit A/D.

Digital Outputs

two digital outputs, relay

contacts rated at 3A resistive @ 24VAC.
Configured as normally open.

Output Resolution

8 bit D/A.

Communication

156 kbps ARCNET, 9600

bps or 38.4 kbps CMnet; twisted pair
wiring.

Environmental Operating Range

0° to

130°F (-17.8° to 54.4°C); 10 to 90%
relative humidity, non-condensing.

Status Indication

Visual (LED) status of

CMnet communication, running, errors,
and power. (For UUKL Smoke Control
Systems, 32 to 120.2 °F [0 to 49 °C]; 10 to
85% relative humidity, non-condensing.)

Memory

512KB Flash memory and 512KB

non-volatile battery-backed RAM.

Protection

Voltage, current, and ESD

protection on incoming power and
CMnet.

Battery

Seven-year lithium BR2325 battery

provides a minimum of 10,000 hours of
data retention during power outages.

Listed by

UL 916 (PAZX), cUL C22.2 No.

205-M1983 (PAZX7), FCC Part 15 -
Subpart B - Class A.

Mounting

Screw the M220nx into an enclosed panel
using the mounting holes provided on the
cover plate. Be sure to leave about 2 inches (5
centimeters) on each side for wiring.

Addressing

Before setting or changing the address, make
sure the M220nx’s power is off. The M220nx
only reads the address when the module is
turned on. After changing the address, you
must transfer memory to the module. Refer to
“Transferring Memory” on page 8.

The M220nx has two rotary switches for
assigning the module’s CMnet address. One
switch corresponds to the tens digit and the
other corresponds to the ones digit. For
example, if the module’s address is three, set
the tens switch to zero and the ones switch to
three, as shown in Figure 2.

Power Wiring

Whenever possible, make sure the module’s
power and communications connections are
working properly before connecting any input
or output points.

CAUTION

The M220nx module is a Class 2

device (less than 30VAC, 100VA maximum).
Take appropriate isolation measures when
mounting the M220nx module in a control
panel where non-Class 2 devices (for
example, 120VAC) or wiring are present.

You can power several modules from the
same transformer if you maintain the same
polarity.

Figure 2. Setting the module’s address

10's

1's

Summary of Contents for M220NX

Page 1: ...n BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions M220nx Using the M220nx 2 Specifications 3 Mounting 3 Addressing 3 Power Wiring 3 CMnet Communications 4 Using the M220nx on an ARC156 CMnet 4 Using the M220nx on a 9600 or 38 4K bps CMnet 4 To connect the M220nx to the CMnet 5 Communicating with the W...

Page 2: ...signed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to Figure 1 Modu...

Page 3: ...ention during power outages Listed by UL 916 PAZX cUL C22 2 No 205 M1983 PAZX7 FCC Part 15 Subpart B Class A Mounting Screw the M220nx into an enclosed panel using the mounting holes provided on the cover plate Be sure to leave about 2 inches 5 centimeters on each side for wiring Addressing Before setting or changing the address make sure the M220nx s power is off The M220nx only reads the address...

Page 4: ...t at 156 kbps The ARCNET CMnet configuration provides BACnet compatibility as well as better performance over a legacy CMnet All modules on a CMnet must communicate at the same speed When communicating at 156 kbps the CMnet uses a unique implementation of the industry standard ARCNET protocol called ARC156 For a summary of the differences between ARCNET and ARC156 please refer to the 156K CMnet Wi...

Page 5: ...o the EIA 232 port of the APT using a standard straight through serial cable 2 Set the APT s Mode Select switch On an ARC156 CMnet use the TTL setting On a legacy CMnet use the 485 setting 3 Connect the Access Port of the APT to the Access Port of the module 4 In SuperVision define the connection type using Table 1 Inputs The M220nx module has two universal inputs to accept the types of signals li...

Page 6: ...xternal 24VAC power supply connect one leg of the 24VAC supply to the module ground 3 Set the configuration jumper for each input to indicate the type of input used Make sure the jumper is positioned correctly and be sure to grip the jumper by the sides only See Figure 5 on page 7 4 For each input enter the channel number offset and gain on the Function Block s Parameter page in SuperVision Valid ...

Page 7: ...nel Numbers The following tables show the valid channel numbers for each point on the M220nx Enter the channel number offset and gain for each point in Eikon before the Function Block is made or on the FB s Parameter page in SuperVision If an offset and gain are not provided here use SuperVision s Point Configuration or Point Help feature to determine the offset and gain Figure 5 Jumper Position F...

Page 8: ...t the module to try to restore communication Formatting the module erases all memory so you need to transfer memory back to the module once it is formatted 1 Turn the module s power off Make sure the module s address switches are not set to 0 0 2 Press and hold the Format button see Figure 1 on page 2 for location 3 While continuing to hold the Format button turn the module s power on 4 Continue t...

Page 9: ...l Production Date To determine when a module was manufactured check the module status report for the module in SuperVision Refer to the SuperVision User s Guide for more information about the module status report A sticker on the back of the module also shows the date the module was manufactured The first three characters on the sticker indicate the type of module The next three characters show th...

Reviews: