Automated Logic LGE Technical Instructions Download Page 4

Revised 12/22/99 • LGE

4

© 1999 Automated Logic Corporation

Before setting or changing the address, make
sure the LGE’s power is off. The LGE only
reads the address when the module is turned
on. After changing the address, you must
transfer memory to the module. Refer to
“Transferring Memory” on page 6.

IP Addressing

TCP/IP must be set up on the workstation
with an active IP address before configuring
the module’s IP address (refer to

TCP/IP Setup

for SuperVision

for a detailed procedure).

You can use a default IP address for the LGE
that is created by the module, or assign an IP
address if required by the customer. The IP
Addr switch (see Figure 2 on page 3)
determines which IP address is used.

• Default: When the IP Addr DIP switch

is set to Default, the following IP
networking parameters are
automatically set on the CEM Parameter
page:

IP Address = 192.168.168.XXX, w

here

XXX is the LGE’s LGnet address (see
“LGnet Addressing” on page 3).

Subnet Mask = 255.255.255.0

Default Gateway Address =

192.168.168.254

NOTE

The default gateway address is

an intranet address. This means that
data packets from this address are
dropped by all internet routers and are
not sent beyond the local network
segment.

• Assigned: When the IP Addr DIP

switch is set to Assigned, you must set
the above parameters on the CEM
Parameter page.

Use the following procedure to set the IP
address when using the Default mode:

1. Set the IP Addr DIP switch to Default.

2. Turn the LGE’s power on.

3. If using SuperVision v2.6, edit your HOSTS

file to include the following line for each
gateway (see

TCP/IP Setup for SuperVision

for a detailed procedure):

192.168.168.x

Where x is the gateway’s address as
defined in “LGnet Addressing” on page 3.

4. If using SuperVision v2.6, run Setup.exe

on the disk shipped with your LGE.

This setup copies updated Portman files to
your emsys folder.

5. Configure the connection as Network in

SuperVision Plus v3.01 or NetBIOS in
SuperVision v2.6.

Use the following procedure to set the IP
address when using the Assigned mode:

1. Obtain an IP address from the job site’s

Network Administrator.

2. Establish communication with the LGE

through SuperVision using one of the
connection types in Table 1.

3. Enter the following information, provided

by the Network Administrator, on the CEM
Parameter page:

• the Assigned IP Address

Table 1. Connecting with the Workstation

Port

Cable

SuperVision
v3.01

SuperVision
v2.6

Ethernet

10baseT

Network

NetBIOS

Access Port

APT

Access Port

Direct
Network

Console
Port

DC95, DC99,
or APT

Direct
Connect

Direct
Connect

Summary of Contents for LGE

Page 1: ...Corporation InterOp is a trademark of Automated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical I...

Page 2: ...ion The LGE uses the CEM module driver for more information see the CEM Module Driver document on the Automated Logic website at www automatedlogic com CAUTION Changes or modifications to this unit no...

Page 3: ...net Console Port 1 and Ethernet communications errors running and power Memory 1 MB flash 1 MB RAM Protection Built in surge and transient protection circuitry Battery 7 year lithium BR2325 battery pr...

Page 4: ...d the local network segment Assigned When the IP Addr DIP switch is set to Assigned you must set the above parameters on the CEM Parameter page Use the following procedure to set the IP address when u...

Page 5: ...s the module from being powered up before the proper voltage is verified 2 Make sure the 24VAC power source is off 3 Connect the power wires to the module s power terminals labeled Ground and 24VAC se...

Page 6: ...erVision v3 0 click Tools Troubleshooting Module Status To view the module status report in SuperVision v2 6b press the Esc key type MO module address 15 and press Enter 3 Transfer memory to the modul...

Page 7: ...l the Error LED flashes three times in sync with the Run LED 4 Release the Format button 5 Transfer memory to the module Refer to Transferring Memory on page 6 Figure 5 Wiring Diagrams Figure 6 Using...

Page 8: ...ion Refer to the SuperVision User s Guide for more information about the Module Status report A sticker on the back of the module also shows the date the module was manufactured The first three charac...

Reviews: