Revised 7/10/01 • InterOP8500
11
© 2001 Automated Logic Corporation
1. Turn the Johnson panel power switch off.
2. Determine the type of signal received by
the field termination board. Consult the
Johnson Controls manuals if necessary.
The InterOP8500 must be configured to
receive the same type of input as the
previously removed Johnson boards.
3. Set the InterOp8500 jumpers as follows:
• For RTD mode insert a jumper for the
individual input. The jumpers are
located along the lower right side of the
InterOP8500 board (see Figure 13).
NOTE
NOTE
NOTE
NOTE If using a solid-state current
switch on a digital input, the resistance
must drop low enough for the module to
recognize it.
• For voltage and potentiometer mode,
remove the jumpers. (Current mode can
be configured by adding an external
sense resistor. For 4-20mA use a 250
ohm resistor Figure 14). Turn the
InterOP8500's power switch on.
Figure 13. Analog Input Jumpers
U nsw itched Inputs
Jum p er in P la ce =
RTD M o d e
Sw itched Inputs
Jum p e r R e m ove d =
V oltag e M ode
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Grip
He re
Figure 14. Analog Input Wiring for 4-20 mA Signal
InterOp8500
As specified by the
sensor manufacturer.
Sensor
120 VAC
XX VAC
ungrounded
Isolated
DC Power
Supply
4-20mA
Transducer
250 ohm
resistor
Connect to Analog Input
Connect to Analog Common (unswitched)
Field Termination
Board