Automated Logic DIAG485 Technical Instructions Download Page 3

 Figure 2. Sample CMnet Configuration

Segment

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

D

R

T

T

P

Segment

Segment

T

T

T

T

M

M

M

M

M

M

M

M

M

P

P

P

P

P

R

D

D

M

= Module

= REP485

= 120 Ohm

terminators

= DIAG485

= PROT485

= Earth Ground

R

T

D

P

M

Revised 7/24/03 • DIAG485

3

© 2003 Automated Logic Corporation

Diagnosing Network 

Problems

Figure 3 explains the meaning of some of the 
signals you may see on the DIAG485. The 
length of the network segment affects these 
displays; on a lengthy segment, fewer LEDs in 
each column may be illuminated. Likewise, 
on a short segment, more LEDs may be 
illuminated.

 Figure 3. Reading DIAG485 LED Signals

Net - Net +

Good communications

One terminator missing

Both terminators missing

No terminator, no bias

Off

On

Properly
terminated, no bias

Too many terminators,

or excessive cable length

Adding Bias

The Bias jumper on the DIAG485 board (see 
Figure 1) determines whether network bias is 
added. Only one DIAG485 per network 
segment can have the Bias jumper in place. 
The DIAG485 with the Bias jumper should be 
placed in the middle of the segment.

Additional DIAG485s with the Bias jumper 
removed may be used on a segment for 
monitoring the network communications.

Protection

The DIAG485 is protected by an internal solid 
state Polyswitch on the CMnet. This 
Polyswitch is not replaceable and will reset 
itself if the condition that caused the fault 
returns to normal. 

Reviews: