Installation Instructions:
Position the heater on a flat, level, non-flammable, solid surface.
Direct-fired heaters are intended for use in outdoor open areas or in
indoor well ventilated areas. For indoor use, provide permanent ventilation
openings of at least 25 cm²/kW, equally distributed between floor and high
level, with a minimum of 250 cm².
BGO1601-10 BGO1601-20 BGO1601-30 BGO1601-50
Minimum Opening Size 260 cm²
600 cm²
800 cm²
1250 cm²
•
Only install the heater in normal upright position.
•
Do not place the heater near walls, corners or low ceilings.
•
Do not place the heater below a socket outlet.
•
Do not place the heater on moving vehicles or where it can tip over.
•
Keep the heater away from flammable, combustible, explosive or
corrosive materials.
•
Keep the heater away from curtains or similar materials that could
block the air inlet and outlet.
•
Never block or restrict the air inlet and outlet for any reason.
•
Keep the power cable away from heat sources, sharp edges, cutting
and moving parts.
•
Do not expose directly to the weather or to excessive humidity.
•
Do not place the heater in the immediate surroundings of a bath,
shower or swimming pool.
•
Follow general and special fire safety regulations in force in all fields
of applications. In any case ensure the following minimum safety clearances
from materials or objects in the surroundings of the heater:
•
Side:
0.6 m
•
Air inlet side:
1 m
•
Top:
1.5 m
•
Hot air outlet side:
3 m
•
Floor:
0 m
•
Floors and ceilings must be made of fireproof materials in the place
where the heater is operated.
•
Do not connect direct-fired heaters to air ducts.