1 Sensors
Page | 25
MM Application Possibilities
1.4
Steam Pressure Sensor
Steam Pressure Sensor MM
Blue (3)
T37
White (2)
T38
Brown (1)
T39
For correct operation the detector must be installed with a pressure siphon loop.
Do not install an isolation valve between the detector and the pressure vessel.
IP
65
NEMA
4
Torque Setting
15-20Nm
O-ring material
Viton
Max storage temp
-25°C to +85 °C (-13
O
F to 185
O
F)
Max operating temp
-25°C to +85 °C (-13
O
F to 185
O
F)
Media temp (steam)
-25°C to +85 °C (-13
O
F to 185
O
F)
Part No
Actual Range
Over Pressure
Burst Pressure
MM10010 (U)
0 – 3.4 bar (0 – 50 PSI)
8 bar (116 PSI)
12 bar (174 PSI)
MM10008 (U)
0 – 20 bar (0 – 300 PSI)
50 bar (725 PSI)
75 bar (1087 PSI)
MM10009 (U)
0 – 34 bar (0 – 500 PSI)
80 bar (1160 PSI)
100 bar (1450 PSI)
MM10017 (U)
0 – 100 bar (0 – 1450 PSI) 200 bar (2900 PSI)
300 bar (4351 PSI)
Plug fits correctly in one position only, do not force.
Do not use case to tighten pressure connection.
Maximum 2.5mm flat blade screwdriver for electrical connections
PG 7 Cable Entry
27mm (1 1/16”)
across flats
1/4” NPTT
Drawing No. 9033
Summary of Contents for Mk8 MM
Page 1: ...Combustion Management Systems MM APPLICATION POSSIBILITIES Technical Manual 18 12 2019...
Page 8: ...1 Sensors Page 2 MM Application Possibilities Gas Pressure Sensor...
Page 27: ...1 Sensors Page 21 MM Application Possibilities Air Pressure Sensor...
Page 32: ...1 Sensors Page 26 MM Application Possibilities Steam Pressure Sensor...
Page 36: ...1 Sensors Page 30 MM Application Possibilities Outside Temperature Sensor...
Page 37: ...1 Sensors Page 31 MM Application Possibilities Outside Temperature Module...
Page 38: ...1 Sensors Page 32 MM Application Possibilities Outside Temperature Module Wiring...
Page 42: ...2 Flame Safeguard Page 36 MM Application Possibilities 2 1 1 Interrupted Pilot Gas...
Page 43: ...2 Flame Safeguard Page 37 MM Application Possibilities 2 1 2 Interrupted Pilot Oil...
Page 46: ...2 Flame Safeguard Page 40 MM Application Possibilities IR End View Scanner...
Page 72: ...2 Flame Safeguard Page 66 MM Application Possibilities 2 9 3 Wiring...
Page 81: ...5 Intelligent Boiler Sequencing Page 75 MM Application Possibilities 5 1 3 Hot Water Example...
Page 83: ...5 Intelligent Boiler Sequencing Page 77 MM Application Possibilities 5 1 5 IBS Communications...