TrueAlert ES Addressable Ceiling Mount Visual Indoor Notification Appliances Installation Instructions
Setting the strobe candela setting
1.
The jumpers are factory set to FACP. Use this setting when programming the candela setting at the 4100ES FACP. The candela setting is visible
through the slot on the side of the appliance.
2.
For manual selection, remove the cover and slide the CD selector to the required setting:
- FACP or 15/30/75/110 for standard strobes
- FACP or 185/135/110 for HiCD strobes.
- FACP or 95/110/135 for amber strobes.
- FACP or 75/95/110 for blue strobes.
3.
When the appliance is mounted, the candela rating is visible through the slot on the side of the appliance.
Note:
To avoid a programming mismatch trouble, ensure that one of the 4 candela outputs is programmed for each appliance by authorized service
personnel. To set the candela using the Programmer set it to FACP. For more information refer to the
4100ES Programmer’s Manual
(574-849AC).
Figure 6: Setting the strobe and appliance configuration