TrueAlert ES Addressable Ceiling Mount Visual Indoor Notification Appliances Installation Instructions

Setting the strobe candela setting

1.

The jumpers are factory set to FACP. Use this setting when programming the candela setting at the 4100ES FACP. The candela setting is visible

through the slot on the side of the appliance.

2.

For manual selection, remove the cover and slide the CD selector to the required setting:

- FACP or 15/30/75/110 for standard strobes
- FACP or 185/135/110 for HiCD strobes.
- FACP or 95/110/135 for amber strobes.
- FACP or 75/95/110 for blue strobes.

3.

When the appliance is mounted, the candela rating is visible through the slot on the side of the appliance.

Note: 

To avoid a programming mismatch trouble, ensure that one of the 4 candela outputs is programmed for each appliance by authorized service

personnel. To set the candela using the Programmer set it to FACP. For more information refer to the 

4100ES Programmer’s Manual

 (574-849AC).

Figure 6: Setting the strobe and appliance configuration

Summary of Contents for TrueAlert ES

Page 1: ...cation reference Type Models Cover colors Operation TrueAlert ES Ceiling Mount Visible Only VO Appliance Components A49VO APPLC A49VO APPLC BA A49VOH APPLC A49VOH APPLC BA A49VOH APPLCA A49VOH APPLCA BA A49VOH APPLCB A49VOH APPLCB BA Accessories 49VO APCS Covers A49VOC CRALT A49VOC CRBF A49VOC CRFEU A49VOC CRF A49VOC CRS A49VOC CWALT A49VOC CWBF A49VOC CWFEU A49VOC CWF A49VOC CWS A49VOC CK A49VOC ...

Page 2: ...ch pounds 3 Ensure that correct polarity is maintained for each strobe unit Note Signal line circuit SLC wiring must be twisted pair TWP CKT Terminals accept two Wires 12 18 American wire gauge AWG TWP Important Do not bring the conduit through the rear of the electrical box Strip the lead insulation to 7 16 inch maximum Figure 3 Wiring instructions Wiring guidelines Assign a maximum of 127 active...

Page 3: ...IDNAC notification appliance has a unique address that is set using an eight position DIP switch ADDR1 Assign up to 127 unique addresses to an SLC but the total appliance loading available may be less due to appliance current requirements For legacy fire panel models Autocall 4009T and 4100 TPS only addresses 1 to 63 are available To set the address complete the following steps 1 Insert a slotted ...

Page 4: ... to the required setting FACP or 15 30 75 110 for standard strobes FACP or 185 135 110 for HiCD strobes FACP or 95 110 135 for amber strobes FACP or 75 95 110 for blue strobes 3 When the appliance is mounted the candela rating is visible through the slot on the side of the appliance Note To avoid a programming mismatch trouble ensure that one of the 4 candela outputs is programmed for each applian...

Page 5: ...in any way Table 2 Maximum RMS operating current 17 31 VDC Candela Current 15 73 mA 30 114 mA 75 210 mA 110 269 mA Table 3 Maximum RMS operating current 23 30 VDC 49 VO Visible 49 VOH Visible Candela Candela Current CD amber CD blue CD clear Current 15 55 mA 30 83 mA 90 75 110 253 mA 75 153 mA 110 95 135 296 mA 110 199 mA 135 110 185 377 mA Table 4 Specifications Vertical and horizontal light disp...

Page 6: ...ditional listings may be applicable contact your local Autocall product supplier for the latest status Listings and approvals under Tyco Fire Security GmbH and the product names listed in this material are marks and or registered marks Unauthorized use is strictly prohibited NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association NFPA ...

Reviews: