Page 31
579-1165AC Rev C
4007ES Operator’s Manual
Table 6: Report Menu Screen Buttons
Button
Description
TrueAlarm Service
Tap the
TrueAlarm Service
button to generate a report which contains the following information:
• Device Number
• Custom Label
• Alarm Level (sensitivity level of the device)
• Average Value
• Current Value
• Percent of Alarm: Shows the current value for the sensor. Value is shown as a percentage of 100% (alarm). For
example, if the value shown is 9%, it means that the sensor is currently at 9% of the value required to trigger an
alarm.
• Peak Value: Shows the highest value that the sensor has reached. Value is shown as a percentage of 100% (alarm).
For example, if the value shown is 9%, it means that the peak value experienced by the sensor was 9% of the value
required to trigger an alarm.
• Current State: Possible values include Normal, Trouble, Dirty, Excessively Dirty, and Almost Dirty.
TrueAlert NAC Test
Tap the
TrueAlert NAC Test
button to generate a report which contains the following information for each TrueAlert
device:
• Point ID
• Custom Label
• Device Type
• Candela
TrueAlert Status
The TrueAlert Status Report can be created after the TrueNAC Voltage Drop Test is run.
Tap the
TrueAlert Status
button to access the
Print TAlert Status
screen. The
All
button can be used to generate the
report containing the status for all devices. The
Last
button can be used to generate a report containing the status of
the last test. The report contains the following information:
• Point ID
• Custom Label
• Pass/Fail
TrueAlarm CO
Tap the
TrueAlarm CO
button to generate a report with the following information regarding the TrueAlarm CO devices:
• Device Number (on the network)
• Custom Label (custom description of the device)
• Current Device Value (PPM)
• End-of-Life Date
• Device Status (Normal, Trouble)
Active List
Tap the
Active List
button to access the
Print Active List
screen, where the
Install Mode
button can be used to
generate a report containing the following Install Mode list information:
• Point ID
• Custom Label
• Device Status
Verification Tally
Tap the
Verification Tally
button to generate a report containing the following information for each device supporting
the alarm verification:
• Device Number
• Custom Label
• Device Type
• Point Type
• Tally Count
TrueAlert Self-Test
Tap the
TrueAlert Self-Test
button to access the
Print TA Self-Test
screen to generate a report containing the Self-Test
results for the TrueAlert appliances. Tap the
ALL
button to generate a report with the results for all appliances. Tap the
LAST
button to generate a report with result for the last device