Installation Manual 

 SDU 404 

 

Page 7  

 

Shutdown Override Disabled 

Enable this if the event shall be 

triggered even if SDU is in shutdown 

override state. 

This is typical for a manual E-stop 

button. 

Delay before Load Reduction 

Set the number of seconds until load 

reduction. 

Delay before Shutdown 

Set the number of seconds until 

shutdown. 

Initial Delay 

Set the number of seconds until switch 

channel is activated for monitoring. 

The “Initial Delay” countdown starts 
when all criteria (“

Engine is running

” 

and “Speed Limit”) are met.

 

Speed Limit Enabled 

Set if Speed limit is enabled or not. The 

actual engine speed is set in the Speed 

limit [RPM] section. 

Speed Limit [RPM] 

 

If the engine speed is above the 

set value, then the channel is 

enabled. 

 

If the engine speed drops 50 

RPM below the set value, then 

the channel is disabled. 

Miscellaneous 

 

Set input voltage warning levels. 

 

Enable “Allow Load Reduction 
Override” to override load 

reductions via the shutdown 

override switch. 

 

Enable “Automatic Buzzer Off” to 

make the SDU buzzer silence 

automatically after five seconds. 

 

“Shutdown Override Switch” and 
“Acknowledge Switch” 

configuration. 

 

Output Functions 

Configuration of relays and digital 

output. 

Synchronize 

Synchronization of DCU and SDU 

configuration. 

 

 

 

Summary of Contents for SDU 404

Page 1: ...Manual 1100413 Installation Manual SDU 404 Shutdown Unit...

Page 2: ...based on former QIG 1 1 21 03 16 Added Appendix A and minor updates 1 2 11 08 17 Added DCU 210E 208E to the DCU Communication terminals table Copyright 2017 by Auto Maskin AS All rights reserved No pa...

Page 3: ...ine Control Unit 2 RP 410 210E Remote Panel 2 Ethernet Switch 2 Expansion 2 INSTALLATION 3 GENERAL 3 LED Overview 3 WIRING 4 24VDC Supply 4 Switch Channels 4 DCU COMMUNICATION 5 BUTTONS 5 Acknowledge...

Page 4: ...installation work is carried out in a satisfactorily manner that it is operationally in good order that the approved material and accessories are used and that the installation meet all applicable ru...

Page 5: ...action is also here RP 410 210E Remote Panel The optional RP remote panel brings the DCU display to a remote location with no need for any configuration Ethernet Switch It s recommended to always us a...

Page 6: ...has a brief description LED Description Power Lit when power supply is OK Flashing when below the configurable very low threshold Green Running Lit when engine is running Green Overspeed Unacknowledge...

Page 7: ...tor connected across Note The 10k resistors shall be connected directly at the switch and not at the SDU 404 Switches shall be normally open NO and shall close to indicate engine shutdown Short Circui...

Page 8: ...meters The Baud rate is 19200 baud 8 data bits 1 stop bit Even parity Configuration Mismatch Warning When the SDU is connected to the DCU the DCU will analyze the configuration in the SDU and compare...

Page 9: ...ersion This page give the information about the hardware and software version of the SDU 404 Speed Sensor This page has the configuration of the pickup channel Switch This page has the configuration f...

Page 10: ...met Speed Limit Enabled Set if Speed limit is enabled or not The actual engine speed is set in the Speed limit RPM section Speed Limit RPM If the engine speed is above the set value then the channel...

Page 11: ...Installation Manual SDU 404 Page 8 Appendix A Wiring The diagram below shows recommended wiring including 3 different types of Switch inputs...

Page 12: ...Installation Manual SDU 404 Page 9 Appendix B Front Front side and Connectors DCU Link Switch input 1 4 Shutdown Override Acknowledge Power Supply MPU Input Shutdown Relay 1 2 Config...

Reviews: