If for instance the LANs subnet is 192.168.230 and the DHCP’s IP address range is set to 50
– 210, valid IP addresses of the DCU would be for instance 192.168.230.211, 192.168.230.7
or 192.168.230.231.
Do not use the DCU built-in DHCP-server (the Menu / Connect a PC… menu entry) in a LAN
with its own DHCP server, since two DHCP servers in the same LAN may create conflicting
IP addresses.
2.2.2.5 Connection to a LAN using Fixed IP Addresses
Set the IP address of the DCU to a free/available IP address within the LAN’s subnet.
2.2.2.6 Factory Defaults for the DCU
Factory defaults are valid at initial startup only.
● IP address: 192.168.0.101
● Subnet Mask: 255.255.255.0
● Default Gateway: 192.168.0.1
For later resets, the current IP configuration will be kept even through the manual Factory
reset operation.
DHCP IP address range: 101 – 199 within the subnet defined by the DCUs IP address.
2.2.2.7 IP Address Conflict
Two or more DCU units with the same IP address should not be connected in the same
network. The result may be that a PC or RP 410E remote panel will be able to address one
of the DCU units only.
Change the IP addresses until all units have a unique address.
2.3 Web Server Configuration
Once logged in, the DCU can be configured. The following are the Web Server main menu
items.
This chapter is not applicable for the RP products.
When logged in, the browser displays the following.