< 1.4 >   Power Sources Connection

Don’t exceed the outlet, branch or phase 
limitations

All electrical power and power control wiring 
must be installed by a quali

fi

 ed electrician and 

comply with local and national regulations.

Step 1  :  Before Power Source Connection

   

 

                   

This Transfer Switch requires that the applied AC waveforms from 
both power sources be in phase with respect to each other. Failure to 
do so can potentially damage the unit and create an unexpected
 

HIGH VOLTAGE 

to be present on the pins of either the Primary Source or Secondary 
Source plug when disconnected, or on the Primary Source or Sec-
ondary Source output receptacles.

For questions concerning this requirement please contact
Austin Hughes Technical Support.
E-mail : [email protected]

Plug the male end of the power cord into the  AC power source.

Step 2  :  Power Source Connection

   

 

                   

After the power source connection, the ATS input power LEDs ( primary & secondary input ) will indicate the 
power ON / OFF status. Then slide the input preference switch to the primary input. 

Power Source Association

  

Primary                   

Input  /  LED

Secondary            

Input  /  LED

Output                    

Power  Source

ON

ON

Primary

OFF

ON

Secondary

ON

OFF

Primary

OFF

OFF

OFF

< 1.5 >   Devices Connection

Step 1  :  Before connect the devices to the ATS outlet, please keep the device's on / off      

                switch in the off position.

 

Step 2  :  After connect the devices to the ATS outlet, please power on the device. 

Step 3  :  Fasten device's power cord to the cord retention tray with cable ties. 

Do not exceed the ATS maximum current loads.

P.4

Summary of Contents for Infra Power ATS-H10C13-10A_C14

Page 1: ...om UM IP ATS Q218V1 Inspired by Your Data Center User Manual Automatic Transfer Switch Designed and manufactured by Austin Hughes 230V Amp 10A 16A Outlet C13 C19 208V Amp 20A Outlet C13 C19 110V Amp 15A 20A Outlet US NEMA ...

Page 2: ...ce personnel should open the chassis Opening it yourself could damage the equipment and invali date its warranty If any part of the equipment becomes damaged or stops functioning have it checked by qualified service personnel What the warranty does not cover Any product on which the serial number has been defaced modified or removed Damage deterioration or malfunction resulting from Accident misus...

Page 3: ...on 2 1 230V ATS 2 2 208V ATS 2 3 110V ATS Content Page 1 2 3 4 4 5 7 9 The equipment comes with the standard parts shown in package content Check and make sure they are included and in good condition If anything is missing or damaged contact the supplier immediately Unpacking Rackmount ATS unit x 1 Mounting Bracket set of 3 x 1 M3 2 4 5 mm screw x 12 Part I ATS Installation Connection 1 1 Package ...

Page 4: ...dary source without power interruption and downtime The entire ATS series are de signed with a local current meter to easily observe power status and device load 1 2 Product Overview Power Current A Automatic Transfer Switch Input Preference 1 2 3 1 2 3 5 4 Local Current Meter 6 Primary Input Secondary Input Input Preference Switch Circuit Breaker Power LED primary input Power LED secondary input ...

Page 5: ...a suitable cabinet or on a stable surface Make sure the place has a good ventilation is out of direct sunlight away from sources of excessive dust dirt heat water moisture and vibration Before Installation Use the provided screws to attach the mounting bracket set set of 3 Step 1 1 M6 screw Use the M6 screw set to secure the ATS to your rack M6 screws not provided Step 2 2 Cable tie Use the cable ...

Page 6: ...or questions concerning this requirement please contact Austin Hughes Technical Support E mail support austin hughes com Plug the male end of the power cord into the AC power source Step 2 Power Source Connection After the power source connection the ATS input power LEDs primary secondary input will indicate the power ON OFF status Then slide the input preference switch to the primary input Power ...

Page 7: ..._EN 1U C13 x 8 EN16 60309 input plug ATS H10C13 16A_EN 1U C13 x 10 ATS H12C13 16A_EN 2U C13 x 12 ATS H16C13 16A_EN 2U C13 x 16 ATS H20C13 16A_EN 2U C13 x 20 ATS H8C13 1C19 16A_EN 1U C13 x 8 C19 x 1 ATS H16C13 2C19 16A_EN 2U C13 x 16 C19 x 2 Model List 16 Amp Height Outlet Inlet x 2 3M cord attached ATS H8C13 16A_C20 1U C13 x 8 C20 input plug ATS H10C13 16A_C20 1U C13 x 10 ATS H12C13 16A_C20 2U C13...

Page 8: ... voltage 10 nominal Input frequency 50 60Hz Inlet plug cord 2 x C14 C20 EN16 60309 plug with 3 meter cord Outlet connectors Multiple C13 C19 outlets Local meter 3 digital LED current meter Overload protection 1 x 10 amp circuit breaker for C14 inlet 1 x 16 amp circuit breaker for C20 EN16 60309 inlet Transfer time 10 16ms typical Electrical endurance 1 x 105 operations Power consumption Approx 8VA...

Page 9: ...TS H8C13 20A_L6 20P 1U C13 x 8 L6 20P input plug ATS H10C13 20A_L6 20P 1U C13 x 10 ATS H12C13 20A_L6 20P 2U C13 x 12 ATS H16C13 20A_L6 20P 2U C13 x 16 ATS H20C13 20A_L6 20P 2U C13 x 20 ATS H8C13 1C19 20A_L6 20P 1U C13 x 8 C19 x 1 ATS H16C13 2C19 20A_L6 20P 2U C13 x 16 C19 x 2 2 2 208V ATS Models P 7 ...

Page 10: ...able input voltage 10 nominal Input frequency 50 60Hz Inlet plug cord 2 x L6 20P plug with 3 meter cord Outlet connectors Multiple C13 C19 outlets Local meter 3 digital LED current meter Overload protection 1 x 20 amp circuit breaker Transfer time 10 16ms typical Electrical endurance 1 x 105 operations Power consumption Approx 8VA Environmental Operating temperature 5 to 60 C degree 23 to 140 F St...

Page 11: ...0US 15A_5 15P 1U NEMA x 10 ATS H12US 15A_5 15P 2U NEMA x 12 ATS H16US 15A_5 15P 2U NEMA x 16 ATS H20US 15A_5 15P 2U NEMA x 20 Model List 20 Amp Height Outlet Inlet x 2 3M cord attached ATS H8US 20A_L5 20P 1U NEMA x 8 NEMA L5 20P input plug ATS H10US 20A_L5 20P 1U NEMA x 10 ATS H12US 20A_L5 20P 2U NEMA x 12 ATS H16US 20A_L5 20P 2U NEMA x 16 ATS H20US 20A_L5 20P 2U NEMA x 20 P 9 ...

Page 12: ...erload protection 1 x 15 amp circuit breaker for NEMA 5 15P inlet 1 x 20 amp circuit breaker for NEMA L5 20P inlet Transfer time 10 16ms typical Electrical endurance 1 x 105 operations Power consumption Approx 8VA Environmental Operating temperature 5 to 60 C degree 23 to 140 F Storage temperature 25 to 65 C degree 13 to 149 F Operating humidity 0 95 non condensing Storage humidity 0 95 non conden...

Reviews: