ROUBLSHOOTING

T

ROUBLSHOOTING

Exchanging  a  faulty  drive  in  the  multi-drive 
system:

 

¢

Switch 

off

 the supply voltage (24 V DC).

 

¢

Disconnect  the  connection  cable  from  the  faulty  drive.

 

Do not remove the 

M-COM

.

 

¢

Mount the new / repaired drive and connect it.

 

¢

Switch 

on

  the  supply  voltage  (24 V DC)  -  in 

CLOSE

 

direction.

 

¢

Observe the 

LED

 reaction of the 

M-COM

.

 

¢

Within  10  seconds  the 

M-COM

  signals  „Ready  for

 

operation“ for the confi gured system.

 

¢

If the 

LED

 blinks red, an error is displayed.

 

¢

Reset the 

M-COM

 (see chapter „Reset of 

M-COM

“).

 

¢

Check wiring and the system.

 

¢

Eliminate faults.

 

¢

Put  the  system  -  with 

M-COM

  -  back  into  operation

 

(see chapter „First commissioning“) .

 

¢

If the 

LED

 blinks red, an error is displayed.

 

¢

Reset the 

M-COM

 (see chapter „Reset of 

M-COM

“).

 

¢

Check wiring and the system.

 

¢

Eliminate faults.

 

¢

Put  the  system  -  with 

M-COM

  -  back  into  operation

 

(see chapter „First commissioning“) .

No  adjustment  is  carried  out  in  case  of 

ex-

change  of  drives  with  special  program-
ming

 (e.g. strok

e, speed)!

In case of repair please order an exchange drive with the 
same parameter assignment as that of the faulty drive.

!

T

ROUBLESHOOTING

 

USING

 U

NI

PC

 

¢

Connect  the 

UniPC

  to  the  system  (observe  the

 

information given in the instructions for installation of

 

UniPC

).

 

¢

By 

UniPC

 determine the address of the faulty drive.

 

¢

Individually  disconnect  white  wires  (

WH

)  of  drives,

 

to fi nd out where the fault drive is localized.

 

¢

Switch 

off

 the supply voltage (24 V DC).

 

¢

Disconnect and replace the faulty drive.

 

¢

Switch 

on

  the  supply  voltage  (24 V DC)  -  in 

CLOSE

 

direction.

 

¢

Observe the 

LED

 reaction of the 

M-COM

.

 

¢

Within  10  seconds  the 

M-COM

  signals  „Ready  for

 

operation“ for the confi gured system.

LED display

State

          0,5s - 0,5s - 3s

blinks

 green

 (per drive 1 time)

System is o.k. 

(can be operated)

drives identifi ed
(1 time blinks = identifi ed one drive).

LED display

State

          0,5s - 0,5s - 3s

blinks

 green

 (per drive 1 time)

System is o.k. 

(can be operated)

drives identifi ed
(1 time blinks = identifi ed one drive).

LED display

State

          0,5s - 0,5s - 3s

blinks 

red

 (

X-

times)

When the number of the 
learned drives does not coin-
cide with the number of drives 
now recognized.

F

AULT

: System is 

NOT

 o.k.

drives identifi ed

(1 time blinks = identifi ed one drive).

LED display

State

          0,5s - 0,5s - 3s

blinks 

red

 (

X-

times)

When the number of the 
learned drives does not coin-
cide with the number of drives 
now recognized.

F

AULT

: System is 

NOT

 o.k.

drives identifi ed

(1 time blinks = identifi ed one drive).

<

<

<

<