ROUBLSHOOTING
T
ROUBLSHOOTING
:
Exchanging a faulty drive in the multi-drive
system:
¢
Switch
off
the supply voltage (24 V DC).
¢
Disconnect the connection cable from the faulty drive.
Do not remove the
M-COM
.
¢
Mount the new / repaired drive and connect it.
¢
Switch
on
the supply voltage (24 V DC) - in
CLOSE
direction.
¢
Observe the
LED
reaction of the
M-COM
.
¢
Within 10 seconds the
M-COM
signals „Ready for
operation“ for the confi gured system.
¢
If the
LED
blinks red, an error is displayed.
¢
Reset the
M-COM
(see chapter „Reset of
M-COM
“).
¢
Check wiring and the system.
¢
Eliminate faults.
¢
Put the system - with
M-COM
- back into operation
(see chapter „First commissioning“) .
¢
If the
LED
blinks red, an error is displayed.
¢
Reset the
M-COM
(see chapter „Reset of
M-COM
“).
¢
Check wiring and the system.
¢
Eliminate faults.
¢
Put the system - with
M-COM
- back into operation
(see chapter „First commissioning“) .
No adjustment is carried out in case of
ex-
change of drives with special program-
ming
(e.g. strok
e, speed)!
In case of repair please order an exchange drive with the
same parameter assignment as that of the faulty drive.
!
T
ROUBLESHOOTING
USING
U
NI
PC
¢
Connect the
UniPC
to the system (observe the
information given in the instructions for installation of
UniPC
).
¢
By
UniPC
determine the address of the faulty drive.
¢
Individually disconnect white wires (
WH
) of drives,
to fi nd out where the fault drive is localized.
¢
Switch
off
the supply voltage (24 V DC).
¢
Disconnect and replace the faulty drive.
¢
Switch
on
the supply voltage (24 V DC) - in
CLOSE
direction.
¢
Observe the
LED
reaction of the
M-COM
.
¢
Within 10 seconds the
M-COM
signals „Ready for
operation“ for the confi gured system.
LED display
State
0,5s - 0,5s - 3s
blinks
green
(per drive 1 time)
System is o.k.
(can be operated)
drives identifi ed
(1 time blinks = identifi ed one drive).
LED display
State
0,5s - 0,5s - 3s
blinks
green
(per drive 1 time)
System is o.k.
(can be operated)
drives identifi ed
(1 time blinks = identifi ed one drive).
LED display
State
0,5s - 0,5s - 3s
blinks
red
(
X-
times)
When the number of the
learned drives does not coin-
cide with the number of drives
now recognized.
F
AULT
: System is
NOT
o.k.
X
drives identifi ed
(1 time blinks = identifi ed one drive).
LED display
State
0,5s - 0,5s - 3s
blinks
red
(
X-
times)
When the number of the
learned drives does not coin-
cide with the number of drives
now recognized.
F
AULT
: System is
NOT
o.k.
X
drives identifi ed
(1 time blinks = identifi ed one drive).
<
<
<
<