Aumuller EMB 7300 Series Installation And Commissioning Instructions Download Page 15

15

Installation instruction
SHEV - Control Unit EMB 7300

Connecting Thermo-Maximal detectors in drive line

If the drive line is not correctly terminated with an end 
line module for line monitoring or if the fi xed tempera-
ture heat detector is incorrectly connected, the yellow 
fault indicator „

S

“ will signal a fault after a short whi-

le, unless line monitoring was disabled via the licensed 
software.
If the line monitoring via the licensed software disabled, 
no fault displayed .

Only connect when disconnected from the mains power 
supply! Switch off power supply and secure against
reconnection! 

!

Line length and cross-section A (drives) depend on the type of drive and 
on the number of drives. Line length and cross-section can be determined
according to the following formula:

1 2 3

70C

26

70C

26

70C

26

=

=

-

+

+

-

1 2

Kl.

BU

BN

BU

BN

BU

BN

BK

BK

OG

Formula to calculate

the required wire cross-section of a infeed line

A   = cross-section of line in mm

2

L  = line length in m

= current of connected drives in A

U  = line voltage drop = 2 V DC

A

I

L

2

U

56

mm

2

  =

(total) 

x

x

x

(length infeed line)

(voltage drop)

m

m / (Ω*mm

2

)

Cable installation must be in compliance with applicab-
le legal requirements. The terminal cross-section for the 
drive connection is:
EMB 7300   

  

 

-0101 

    

max. 2,5 mm² (fl exible) 

EMB 7300   

  

 

-0101-T   max. 4,0 mm² (rigid wire)

EMB 7300    

 

 

-0101      max. 4,0 mm² (fl exible)

EMB 7300    

 

 

-0101-T   or

EMB 7300    

 

 

-0102      max. 6,0 mm² (rigid wire)

EMB 7300 

   

 

-0101  

EMB 7300 

   

 

-0102  

EMB 7300 

   

 

-0102

2,5A

 

2,5A

5A

 

5A
5A

 

10A
10A

 

20A

I

NSTALLATION

 

STEP

 2: 

C

ONNECTING

 T

HERMO

-M

AXIMAL

 

DETECTOR

 (

HEAD

 

SENSITIVE

 

FIRE

 

DETECTOR

IN

 

DRIVE

 

LINE

I

NSTALLATION

 

STEP

 2:

C

ONNECTING

 T

HERMO

-M

AXIMAL

 

DETECTOR

 

IN

 

DRIVE

 

LINE

04

2,5 A

5 A

20 A

10 A

!

Drive

24V DC

Drive

24V DC

Drive

24V DC

M

M

M

Install drive line 

end module at the last 

drive in the line!

Colour

BU  = 

blue

BN  =

brown

OG =

orange

BK =

black

Connecting drives
EMB 7300

Terminal

Principle

Head sensitive 

fi re detector

Head sensitive 

detector clip

(without housing)

Drive line

end module

NC

NC

NC

NC

NC

NC

For this trigger method is a software programming
required.

USB

Summary of Contents for EMB 7300 Series

Page 1: ...to EN12101 10 and control panel according to prEN12101 9 SHEV CONTROL UNIT EMB 7300 2 5 A 5 A 10 A 20 A tested electrical control device EMB 7300 with recognition number G 514001 Installation and Comm...

Page 2: ...Maximal detector in drive line INSTALLATION STEP 3 Connection of automatic and manual smoke detectors INSTALLATION STEP 4 Connecting wind and rain sensors INSTALLATION STEP 5 Installing relay plug in...

Page 3: ...nfiguration using the free software of the Control Unit manufacturer USB connection ABBREVIATIONS USB Scale units C Degree Celsius A Amps Ah Amp hours kg Kilogram m Metres min Minutes mm Millimeters N...

Page 4: ...of application This control device is intended for power feeding and con trolling electromotive operated windows in facade and roof areas The prime task of this product in combination with the electr...

Page 5: ...red and active light sensors or pressure mats Contact based anti trap protection 20 ZAA 8 2 Pressure sensitive safety switch strips or Motor current monitoring systems internal and external Hold to r...

Page 6: ...carelessness 01 The planning and calculation of the wiring system is the responsibility of the builder or his agent or the authori zed constructor and must be performed according to the statutory pro...

Page 7: ...Post warning signs During the proper assembly of drives with mounting elements at a window and the connection to an external Control Unit the interfaces resulting from mechanical and electrical perfor...

Page 8: ...ER has no influence on a perfect systems environ ment or object specific systems configuration USB Declaration of Conformity The control device is manufactured and inspected for its intended use in ac...

Page 9: ...ce free back up batteries 2x 12 V 2 3 Ah Part No 541000 Application Compact Control Unit for smoke and heat exhaust ventilation systems operating with 24V DC voltage suitable for staircases TECHNICAL...

Page 10: ...ng steel sheet RAL 7035 light grey Dimensions WxHxD 400 x 300 x 150 mm Connection terminals 1 5 mm Drives 6 mm rigid wire Motherboard 1 SHEV group 2 Vent groups Application Compact Control Unit for sm...

Page 11: ...285 x 122 mm Version 2 5A 5A 400 x 300 x 150 mm Version 10A 400 x 400 x 200 mm Version 20A PREPARING ASSEMBLY TECHNICAL DATA WARNING Important instructions for safe assembly Fully observe all instruct...

Page 12: ...DC for smoke heat exhausting natural ventilation Input for ventilation line 1 max 10 vent buttons Output for drive line 2 only for EMB 7300 5 A 0102 10 A 0102 20 A 0102 Input for ventilation line 2 ma...

Page 13: ...depend on the type of drive and on the number of drives Line length and cross section can be determined according to the following formula Formula to calculate the required wire cross section of a inf...

Page 14: ...10 A nominal current EMB 7300 20 A 2X MAX 10 A nominal current SHEV release in case of fire overrides ventilation No ventilation in the event of a mains power supply failure battery operation SHEV rel...

Page 15: ...s section of line in mm2 L line length in m I current of connected drives in A U line voltage drop 2 V DC A I L 2 U 56 mm2 total x x x length infeed line voltage drop V A m m mm2 Cable installation mu...

Page 16: ...ECTION OF AUTOMATIC AND MANUAL SMOKE DETECTORS 04 OK 11 10 9 8 7 6 5 4 3 2 1 1 1 1 22 5 71 1 13 14 15 16 17 18 19 A S B 1 72 OK 11 10 9 8 7 6 5 4 3 2 1 10 k IN C O M O UT IN C O M O UT IN C O M OU T B...

Page 17: ...n sensors is de activated Before mounting and positioning the wind rain sen sors carefully read the safety and assembly instructions provided with the products They are part of the system documentatio...

Page 18: ...nstallation an connect when disconnected from the mains power supply Switch off power supply and secure against reconnection The motherboard has two slots for using one relay plug in card REL 65 each...

Page 19: ...230V AC 50 60 Hz On the version with front mounted push button the connector may be removed Routing via external fuse and switching component PE BU BU BU 2 x back up battery 2 3 Ah 12V Ensure correct...

Page 20: ...V VGG N L USB Do not remove cover F1 F2 F3 Switching power supply 5A RD RD RD RD RD L L Cover SMOKE VENT N N 225 mm 400 mm 285 mm 300 mm 10 A oder 400 mm 20 A Wiring duct 230V AC 50 60 Hz 230V AC 50...

Page 21: ...free version of the system software version VIEW can be downloaded from the homepage www aumueller gmbh de The software can be installed on a computer notebook or net book Please pay regard to the har...

Page 22: ...onents SHEV systems require a logbook in which all important master data have to be entered prior to operation enable and all operational events during the period in operation The logbook is part of t...

Page 23: ...ged Indicator S has steady light open circuit or short circuit in manual fire alarm faulty power monitoring Indicator S blinks slowly open circuit or short circuit in smoke detector line faulty power...

Page 24: ...B A Z A Z 1 32 33 35 36 37 A Z A Z 1 1 2 2 3 3 1 7 2 USB 1 REL65 2 REL65 BUS Module BUS Wind Rain RM HSE LT 2 F1 A A N N Drive 1 Stecker f r Front Button Drive 2 A Z Reset LT 1 Indicators GN Operatio...

Page 25: ...the operator shall carry out or order a visual inspection at least once and document it in writing in the log book We recommend a maintenance contract with a specialist company authorized by the manu...

Page 26: ...lowing Improper use of the product Improper installation commissioning operation maintenance or repair of the product Operating the product by defect and improper installed or not functioning safety a...

Page 27: ...27 Installation instruction SHEV Control Unit EMB 7300 CERTIFICATES 08...

Page 28: ...28 Installation instruction SHEV Control Unit EMB 7300 CERTIFICATES 08...

Page 29: ...EMB 7300 CERTIFICATES THE VdS APPROVAL INCLUDES THE FOLLOWING CONTROL UNITS EMB 7300 without SHEV button EMB 7300 with orange SHEV button EMB 7300 without SHEV button EMB 7300 with orange SHEV button...

Page 30: ...different Control Unit versions Remark Terminals Drive 1 Drive 2 only version 0102 CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE ZU Operation Fault COM COM OPEN OPEN OPEN OPEN OPEN OPEN Buttons Buttons Buttons...

Page 31: ...free from mistakes and errors All information and data contained in this document are subject to alterations without prior notice Distribution and reproduction of this document as well as the use and...

Page 32: ...n Tel 49 8271 8185 0 Fax 49 8271 8185 250 info aumueller gmbh de 9000017000_V0 1_KW05 14 www aumueller gmbh de AUM LLER AUMATIC GMBH Gemeindewald 11 86672 Thierhaupten Tel 49 8271 8185 0 Fax 49 8271 8...

Reviews: