15.8.3 Diagnosis indications
For indication and operation see page 24, subclause 15.5.5.
48
Part-turn actuators SG 03.3 – SG 04.3
with AUMATIC AC 01.1
Operation instructions
1) Only for actuators with Profibus DP
Menu
Abbreviationindisplay Note
D0
ENDPOS. INPUTS
PULL DOWN INPUTS
Pull Down resistors are used for the inputs of the end position signals (limit
switches) on the logic.
PULL UP INPUTS
Pull Up resistors are used for the inputs of the end position signals (limit swit-
ches) on the logic.
D1
ACTUATOR SIGNALS
NO SIGNAL
no actuator signals set
TSC (DSR)
Torque signal CLOSED in actuator tripped (not stored)
TSO (DOEL)
Torque signal OPEN in actuator tripped (not stored)
LSC (WSR)
Limit switching CLOSED in actuator tripped
LSO (WOEL)
Limit switching OPEN in actuator tripped
THERMAL FAULT
Motor protection tripped. Help:
Wait for cool-down; the signal is then either cancelled automatically or if not,
bring selector switch to position Local and operate push button ‚Reset’. Check
fuse F4.
D2
INTERNAL FAULT
NO INTERNAL FAULT
No internal fault has occurred
THERMISTOR
A fault in the TMS tripping device was detected during start-up. Help: Check
wiring diagram and
MOTOR PROTECTION
(M4108). Check TMS tripping
device.
SELECTOR SWITCH
The selector switch recognition is defective (no Hall sensor is tripped or more
than one Hall sensor is tripped). Help: Check local control board, check me-
chanical attachment of the local controls in the housing
OUTPUT TRANSISTOR
The output of the of the run commands to the relay board is defective, help:
Check logic board and relay board
DP1
1)
CAN
No communication with the Profibus DP interface available. Help: The setting
I/O STACK1
(M4106) must be in accordance with the wiring diagram, check
wiring, check Profibus DP interface.
I/O1 CAN
No communication to parallel interface possible. Help: Setting of
I/O1
STACK1
(M4106) must be in accordance with the wiring diagram, check
wiring, check parallel interface
PHASE DETECTION
The phase sequence detection on the power supply is defective. Help: Check
phase sequence detection, check wiring
24V DC FAULT
The internal 24 V supply of the AUMATIC is not within the supply voltage li-
mits. Help: Check supply voltage, check power supply, check wiring of the
AUMATIC voltage supply.
LOGIC CAN
The logic can not establish communication.
NO REACTION
Fault signal of the reaction monitoring (see page 58)
MODBUS 1 CAN
MODBUS 1 CAN
LOCAL CONTROL FAULT
Hardware fault of the local controls.