16.12.3 Operating time monitoring
This function allows the monitoring of the operating time of the actuator. If
the actuator needs more than the set time (Parameter
MAX. RUN TIME
,
page 33) to move from end position OPEN to end position CLOSED, a
warning signal is given. The actuator is not stopped. When the actuator
moves from an intermediate position to an end position, the set monitoring
time for the whole stroke is converted proportionally according to the partial
stroke to be moved.
To be able to make the settings for operating time or running
time via the display, the setting "
MONITOR TRIGGERS
" (page
44, menu M40) must be in position "
FUNCTION ACTIVE
".
16.12.4 Reaction monitoring
The controls AUMATIC monitor the reaction of the actuator via the control
unit of the actuator.
If no reaction is recorded at the output drive of the actuator within a set time
(parameter
REACTION TIME
, page 42, the actuator is switched off and a
fault signal (collective fault signal) is generated. The triggering of the
reaction monitoring is also indicated in the diagnosis menu.
The fault can be reset with the RESET-button at the local controls. If the
AUMATIC is equipped with a fieldbus interface, the reset can be done via a
reset command from the fieldbus.
No reaction monitoring is performed when operating from an intermediate
position.
The reaction monitoring is set in the factory (parameter
REACTION
MONITORING
, page 44).
16.13 Running indication (blinker)
A signal can be sent to the control station via the signal relays 1 to 5,
indicating whether and in which direction the actuator is running.
Parameter signal relay 1 to 5 "
OPENING BLINK
" and "
CLOSING BLINK
",
pages 30 to 32.
At the local controls the LEDs can indicate whether and in which direction
the actuator is running (see also page 18, subclause 15.4.2) The blinking
indication is switched on or off via the parameter "
BLINKER
", page 28.
16.14 Logging of operating data
Various data are monitored by the AUMATIC and registered by a
non-volatile memory (EEPROM). Two counters are provided, one of them is
erasable. The registered data (see page 42) can be read or deleted via the
display (see page 21, subclause 15.5.4). The access for deletion is
password-protected.
To be able to make the settings for the operational data
logging via the display, the setting "
OPERATIONAL DATA
"
(page 44, menu M40) must be in position "
VIEW ENABLED
".
16.15 Electronic name plate
The electronic name plate registers data of the actuator and the site (see
page 43). If required, the freely definable customer fields, the valve number
and the site number can be changed or entered (see also page 21,
subclause 15.5.4).
To be able to make the settings for the electronic name plate
via the display, the setting "
EL. NAME PLATE
" (page 44,
menu M40) must be in position "
VIEW ENABLED
".
58
Part-turn actuators SG 03.3 – SG 04.3
with AUMATIC AC 01.1
Operation instructions