Standard:
●
–40 °C to +40 °C/+60 °C
For actual version, refer to actuator/controls name plate.
Ambient temperature
1 g, from 10 to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength
may not be derived from this. Not valid in combination with gearboxes.
Vibration resistance according
to IEC 60068-2-6
Open-close duty (operating cycles (OPEN - CLOSE - OPEN):
SA 07.1/07.5 – SA 10.1: 20,000
SA 14.1/14.5 – SA 16.1: 15,000
Modulating duty:
1)
SAR 07.1/07.5 – SAR 10.1: 5.0 million modulating steps
SAR 14.1/14.5 – SAR 16.1: 3.5 million modulating steps
Lifetime
Refer to separate technical data
Weight
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve the modulating accuracy. To
reach the longest possible maintenance and fault-free operating time, the number of starts per hour chosen should be as low as permis-
sible for the process.
1)
13.4
Further information
●
ATEX Directive: (94/9/EC)
●
Electromagnetic Compatibility (EMC): (2004/108/EC)
●
Low Voltage Directive: (2006/95/EC)
●
Machinery Directive: (2006/42/EC)
EU Directives
61
SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
AMExB 01.1
Technical data