Figure 10:
Motor name plate (example)
[1]
Type of current
[2]
Mains voltage
[3]
Mains frequency (for 3-ph and 1-ph AC motors)
Connecting cables
●
For device insulation, appropriate (voltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
●
Use connecting cable with appropriate minimum rated temperature.
●
For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
5.2
Motor connection
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
Motor connection is performed at motor connection compartment [2] for motors with
nominal currents exceeding 25 A. Motor connection can also be made via plug/socket
connector [1] in case of lower nominal currents.
Figure 11:
Connection arrangement for sizes 25.1 – 40.1
[1]
AUMA plug/socket connector for control connections and motor connections
up to 25 A
[2]
Motor connection compartment for motor connections exceeding 25 A
[3]
Cable entry for motor connection
15
SA 25.1 – SA 48.1/SAR 25.1 – SAR 30.1
Electrical connection