Features and functions
Nominal voltages:
1-phase AC current:
100 – 240 V / 50 – 60 Hz
Power supply
Category II in compliance with IEC 60364-4-443
Overvoltage category
With integral motor controller (current consumption in standby mode < 3 W)
Power electronics
3 digital inputs (via opto-isolator, with one common)
●
Control voltage 24 V DC, current consumption: approx. 15 mA per input
●
Minimum pulse duration for shortest operation pulse: 100 ms
●
All digital inputs must be supplied with the same potential
●
All inputs can be configured as required
●
Standard assignment:
CLOSE, OPEN, STOP
●
Assignment for option with positioner:
MODE, OPEN, CLOSE
3 digital in-
puts
Control (input signals)
●
0/4 – 20 mA or 0 – 10 V
●
No galvanic isolation
●
Used as input signal for position setpoint (in combination with positioner) or as input
signal for motor speed
Analogue in-
put
(option)
●
Freely configurable semi-conductor output contacts, per contact max. 24 V DC, 100 mA
(resistive load)
●
Outputs can be configured as required
●
Standard assignment:
End position CLOSED (high active), end position OPEN (high active), collective fault
signal (low active)
3 digital out-
puts
Status signals
(output signals)
●
Position feedback signal 0/4 – 20 mA (load maximum 500
Ω
) or 0 – 10 V
●
No galvanic isolation
Analogue
output
Auxiliary voltage 24 V DC, max. 80 mA for supply of control inputs, without galvanic isolation.
Voltage output (option)
●
Switch-off mode adjustable:
Limit or torque seating for end positions OPEN and CLOSED
●
Torque monitoring across the whole travel
●
Torque by-pass
●
Programmable EMERGENCY behaviour:
-
Digital input low active,
-
Reaction can be selected: Stop, run to end position CLOSED, run to end position
OPEN
●
Speed control
-
Ramps
-
Program operation profiles
-
Programming specific speed for OPEN and CLOSE operations or one digital input
●
Positioner
-
Automatic adaptation of dead band (adaptive behaviour selectable)
Standard:
Functions
●
Positioner
-
Position setpoint via analogue input E1 = 0/4 – 20 mA or 0 – 10 V
-
Programmable behaviour on loss of signal
-
Automatic adaptation of dead band (adaptive behaviour selectable)
-
Selection between open-close duty and modulating duty via digital MODE input
Option:
Bluetooth class II chip, with a range of min. 3 m in industrial environments.
Required accessories:
●
AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC)
●
AUMA Assistant App (Commissioning and Diagnostic Tool for Android and iOS devices)
Bluetooth
Communication interface
Cable entry: 3 x M20x1.5 threads for cable glands.
Inside rail with spring clamp terminals for wire connection.
Electrical connection
Refer to name plate
Wiring diagram (basic version)
46
PF-M25X – PF-M100X
Technical data
Parallel