User level
User level (1), (2), (3), ... defines which menu items or parameters can be displayed
or modified by the active user.
6 different users/user levels are available. User level (1), (2), (3), ... is indicated in
the top display row.
Figure 22: User level display (example user level 4)
Password
A specific password is assigned to each user level and allows different actions. The
password must comprise 6 characters.
Table 13: User level and password
User levels and authorisations
Authorisation/password
User (user level)
Verify settings
No password required
Observer (1)
Change configuration parameters (low level)
Factory password: 000000
Operator (2)
Reserved for future use
Maintenance (3)
Change configuration parameters (high level)
e.g. type of seating, assignment of output contacts
Factory password: 000000
Specialist (4)
Service staff
Change configuration parameters (service level)
Service (5)
AUMA administrator
AUMA (6)
Unauthorised access due to insecure password!
→
We recommend changing the password during initial commissioning.
8.2.3.
Actuator operation from Remote
Risk of immediate actuator operation when connecting to mains!
Risk of death, severe injury or damage to valve.
→
Check operation signals and operation behaviour prior to switching on the mains
voltage.
→
Ensure that the tripping conditions for the failure behaviour are not fulfilled when
switching on.
→
Ensure that the tripping conditions for the EMERGENCY behaviour are not ful-
filled when switching on.
Operation mode REMOTE setting
Operation mode REMOTE is the preliminary condition for actuator control via digital
signals, analogue signals or via fieldbus.
The operation mode can be activated via AUMA Assistant App or AUMA CDT
software:
AUMA Assistant App
DIS_53 Configuration
DIS_2919 Operation mode
PRM_5535 Selector
Or directly via the Remote operation menu in
DIS_2250 Operation function
.
Default setting: Operation mode =
REMOTE
AUMA CDT
DIS_53 Configuration
DIS_2919 Operation mode
33
PF-M25X – PF-M100X
Parallel
Operation