4.
While LED is flashing in blue, hold down push button
for at least two seconds
until the LED is illuminated in red.
➥
The end position CLOSED setting has been successfully completed.
7.1.2.
Set end position OPEN
Electric shock due to presence of hazardous voltage!
Failure to observe this warning results in death or serious injury.
→
Electrical connection and commissioning must be carried out exclusively by
suitably qualified personnel if circuit is live.
→
Do not touch any cables.
1.
Remove cover from actuator.
2.
Operate in direction OPEN via push button until complete valve opening.
Risk of passing set end positions!
→
During operation in directions OPEN/CLOSE, the actuator stops when reaching
the set end position. When pressing again the button, the actuator runs until
reaching a mechanical stop (end stop of the actuator or the valve) or passes
the end position when releasing the button.
➥
The operation in direction OPEN is signalled by the LED flashing in green.
26
PF-M25X – PF-M100X
Commissioning
Parallel