15.

Setting of the electronic intermediate position detection (option)

Any application can be switched on or off via the two intermediate position
switches WDR/LSA and WDL/LSB.

The intermediate position detection is set in the factory according to order
details. If the customer requirements have not been mentioned in the order,
the intermediate positions have been set to 5 mA (WDR/LSA) and 15 mA
(WDL/LSB)
In case other intermediate positions are required they have to be set as fol-
lows:

.

Connect voltage for electronic position transmitter.

.

Take off cover at switch compartment.

.

Move valve to end position CLOSED.

.

Connect ammeter for 0 – 20 mA to measuring points (MP1/ MP2).
(Measured value for normal operation = 0 mA or 4 mA, for inverse opera-
tion = 20 mA)

.

Turn trimmer potentiometer (R9) clockwise, until the yellow LED V9 is no
longer illuminated.

.

Move valve in direction OPEN. Stop the actuator when reaching the desi-
red intermediate position (WDR/LSA).

.

Turn trimmer potentiometer (R9) counter-clockwise, until the yellow LED
V9 is illuminated. The intermediate position WDR/LSA is now set.

.

Move valve to end position OPEN. (Measured value for normal operation
= 20 mA, for inverse operation = 0 mA or 4 mA)

.

Turn trimmer potentiometer (R10) counter-clockwise, until the green LED
V10 is no longer illuminated.

.

Move valve in direction CLOSE. Stop the actuator after reaching the desi-
red intermediate position (WDL/LSB).

.

Turn trimmer potentiometer (R10) clockwise, until the green LED V10 is
illuminated. The intermediate position WDR/LSB is now set.

.

Clean sealing faces at cover and housing; check whether O-ring is in good
condition. Apply a thin film of non-acidic grease to the sealing faces.

.

Replace cover on switch compartment and fasten bolts evenly crosswise.

16

Part-turn actuators SG 03.3 – SG 04.3
AUMA NORM

Operation instructions

MOV

M

Figure K

R6 “0”

MP1 (–)

MP2 (+)

R10

V10 (green) =
WDL/ LSB
reached

M9 (yellow) = WDR/ LSA reached

No

Colour Function

Description

V9

yellow

is illuminated:
WDR/LSA reached

The current, and consequently, the positi-
on have reached the set value

is not illuminated:
no WDR/LSA

The intermediate position WDR/LSA  has
not yet been reached

V10

green

is illuminated:
WDL/LSB reached

The current, and consequently, the positi-
on have reached the set value

is not illuminated:
no WDR/LSB

the intermediate position WDL/LSB has
not yet been reached

Table 6

Summary of Contents for NORM Series

Page 1: ...Electric part turn actuators SG 03 3 SG 04 3 AUMA NORM Operation instructions...

Page 2: ...onnector 9 9 2 Heater 9 9 3 Motor protection 9 9 4 Remote position transmitter 10 9 5 Limit switch 10 9 6 Fitting of the cover 10 10 Setting the limit switching 11 10 1 Setting for end position CLOSED...

Page 3: ...cial attention to safety relevant procedu res in these operation instructions Each is marked by the appropriate picto graph This pictograph means Note Note marks activities or procedures which have ma...

Page 4: ...Manual operation Manual drive for setting and emergency operation handwheel does not rotate during electric operation Handwheel lockable option yes Electrical connection Electrical connection Standar...

Page 5: ...by the heater 5 Packaging Our products are protected by special packaging for the transport ex works The packaging consists of environmentally friendly materials which can easily be separated and rec...

Page 6: ...refer to figure A2 detail A or B ensure that dimensions X Y and Z are observed refer to table 2 Apply non acidic grease at splines of coupling Fit actuator so that fixing holes in actuator and valve...

Page 7: ...x socket head cap screw 21 1 figure B3 Turning clock wise results in smaller turning counter clockwise results in larger swing angles Never remove the screws 21 2 figure B2 and 21 1 figure B3 complete...

Page 8: ...imit switches page 11 in both end positions For this reason the end stops of the actuator have to be set to a slightly larger swing angle approx by 2 larger than the swing angle actually required by t...

Page 9: ...against environmental influences is available see address list page 28 9 2 Heater AUMA part turn actuators have a heater installed as standard To prevent condensation the heater must be connected Refe...

Page 10: ...ing faces at plug cover 26 0 and check whether O ring is in good condition Apply a thin film of non acidic grease e g Vaseline to the sealing faces Replace plug cover 26 0 and fasten 4 bolts 26 01 eve...

Page 11: ...D Press down and turn setting spindle A figure E with screw driver 5 mm in direction of arrow thereby observe switch cam B While a ratchet is felt and heard the switch cam B moves 90 every time When s...

Page 12: ...re F on shaft Move valve to end position CLOSED Turn lower indicator disc until symbol CLOSED is in alignment with the mark on the cover figure L Move actuator to end position OPEN Hold lower indicato...

Page 13: ...od condition Apply a thin film of non acidic grease to the sealing faces Fit and fasten switch compartment cover 14 Setting of electronic position transmitter RWG option For remote indication or exter...

Page 14: ...is felt Turn potentiometer R slightly back from the stop Turn trimmer potentiometer R6 0 clockwise until output current starts to increase Turn back trimmer potentiometer R6 0 until a residual current...

Page 15: ...r rent starts to increase Turn back potentiometer R6 0 until a residual current of approx 0 1 mA is reached Move valve to end position OPEN Set trimmer potentiometer R5 max to end value 16 mA Move val...

Page 16: ...now set Move valve to end position OPEN Measured value for normal operation 20 mA for inverse operation 0 mA or 4 mA Turn trimmer potentiometer R10 counter clockwise until the green LED V10 is no lon...

Page 17: ...ten applying the torques given in table 1 page 5 The gear housing is filled with lubricant in the factory This filling lasts for several years of service 17 Disposal and recycling AUMA actuators have...

Page 18: ...SG 04 3 AUMA NORM Operation instructions S 3 WSR Limit switch closing clockwise rotation S 4 LSO Limit switch opening counter clockwise rotation F 1 TH Thermoswitch motor protection R 1 H Heater R 2...

Page 19: ...19 1 Wiring diagram for SG with 1 phase AC motors Legend page 18 19 Part turn actuators SG 03 3 SG 04 3 Operation instructions AUMA NORM...

Page 20: ...19 2 Wiring diagram for SG with 1 phase AC motors with reversing contactor controls Legend page 18 20 Part turn actuators SG 03 3 SG 04 3 AUMA NORM Operation instructions...

Page 21: ...19 3 Wiring diagram for SG with 3 phase AC motors Legend page 18 21 Part turn actuators SG 03 3 SG 04 3 Operation instructions AUMA NORM...

Page 22: ...S1 S2 17 1 0 5 01 5 1 5 0 8 0 6 0 21 20 2 0 018 8 7 11 23 0 10 0 9 0 24 25 2 3 25 2 2 26 2 2 5 02 08 09 S2 S2 06 13 0 14 0 011 27 0 S1 S2 01 02 010 23 5 23 10 23 3 S1 S2 3 0 23 2 23 6 153 1 153 4 153...

Page 23: ...flange assly 14 0 B Handwheel assly 15 E Cover disc 16 0 B Hex socket head cap screw limit stop assly Type B Sub assembly Type E Component No Type Designation 17 E Screw plug 17 0 B Screw plug assly...

Page 24: ...Notes 24 Part turn actuators SG 03 3 SG 04 3 AUMA NORM Operation instructions...

Page 25: ...Notes 25 Part turn actuators SG 03 3 SG 04 3 Operation instructions AUMA NORM...

Page 26: ...21 Declaration of Conformity and Declaration of Incorporation 26 Part turn actuators SG 03 3 SG 04 3 AUMA NORM Operation instructions...

Page 27: ...Maintenance 3 17 Manual operation 5 Mechanical positon indicator 12 Motor protection 9 Mounting to valve 6 P Parking frame 9 Plug socket connector 9 Position indicator 12 Position transmitter RWG 13 P...

Page 28: ...s dk IBEROPLAN S A ES 28027 Madrid Tel 34 91 3717130 iberoplan iberoplan com D G Bellos Co O E GR 13671 Acharnai Athens Tel 30 210 2409485 info dgbellos gr SIGURD S RUM A S NO 1301 Sandvika Tel 47 67...

Reviews: